Call us 24/7uaedcs@163.com
Welcome to the official website of CNIACS Automation Technology Co., Ltd!
Call us 24/7uaedcs@163.com

TEKTRONIX 5B12N Dual Time Base Plugin

Core characteristics of the instrument and panel controls

1. Core characteristics of the instrument

Dual time base generator: including A time base (main time base) and B time base (auxiliary time base), supporting three working modes (independent sweep, dual sweep, delayed sweep).

Scanning speed range:

A time base: 1 μ s/Div to 5s/Div (21 levels 1-2-5 sequence), 10x magnification (A SWP MAG) to reach 100ns/Div;

B time base: 0.2 μ s/Div to 0.5s/Div (20 levels 1-2-5 sequence), no amplification function.

Delay function: Set the delay time using the DELAY TIME MULT knob, with a range of 0.2-10.2 times the A time base sweep speed (corresponding to 1 μ s to 50s), for delayed sweep mode.

External signal support: External signals can be connected to replace the A time base display, and the amplifier mode provides two calibration deflection coefficients of 50mV/Div and 0.5V/Div.

2. Key panel controls (function summary)

Control Category Control Name Function Description

Mode control MODE (A/B/dual sweep) – A: Only A time base works, B time base is locked

-B: Only B time base works, A time base is locked

-Dual sweep frequency (A+B pressed): A and B time bases work simultaneously, with time sharing display

A INTEN-B DLY’D Delay Sweep Mode Switch, to be coordinated with A/B buttons:

-Only press A: display A time base, B time base works synchronously (strengthened segment display)

-Only press B: B time base delay start (delay time is determined by A time base and DELAY TIME MULT)

-Press A+B: A time base strengthening segment and B time base delay display

B TRIG AFTER DLY is triggered after a delay in the B time base. It is necessary to first meet the delay time set by the A time base, and then activate the B time base with the trigger signal

Time base control A/B Seconds/DIV selects calibration scanning speed, and the knob skirt lights up to display the current gear (A is a dark gray knob, B is a light gray knob)

A SWP MAG A time base is amplified 10 times, and the scanning speed is directly displayed after amplification (such as 1 μ s/Div → 100ns/Div), with only the central grid area visible

DELAY TIME MULT delay multiple adjustment, range 0.2-10.2 times A time base sweep speed, used to locate the starting point of delayed sweep frequency

A SINGL SWP A Time Base Single Sweep Mode, only triggered once when pressed, requires A RESET reset

A RESET resets the sweep circuit: re standby in single mode, terminate the current sweep in any mode

Trigger Control A/B TRIGGERING Source – LEFT/RIGHT: Select the left/right vertical plugin as the trigger source

-COMPOSITE (exclusive to A): Select the display signal as the trigger source (press A+B)

-LINE: Select the power frequency (50/60Hz) as the trigger source

-EXT (unique to A): Select A EXT INPUT external signal as the trigger source

A/B TRIGGERING COUPLING – AC (pressed): Capacitive coupling, blocking DC, attenuating low frequencies<50Hz

-DC (pop-up): Direct coupling, retaining DC and low-frequency components

A/B TRIGGERING SLOPE -+SLOPE (pressed): Positive slope trigger (signal rising edge starts sweep frequency)

— SLOPE (pop-up): Negative slope trigger (signal falling edge initiates frequency sweep)

A/B TRIGGERING LEVEL adjusts the trigger level, and the ± region corresponds to the positive and negative voltage points of the signal. Rotate clockwise to increase the trigger level

Status and display READY INDICATOR indicator light, illuminated in A time base single mode to indicate readiness (trigger acceptable)

Display (ALT/CHOP) – ALT (pop-up): alternately displays A/B time base, suitable for fast scanning speed

-CHOP (pressed): Chopper displays A/B time base, suitable for scenarios with slow scanning speed or large scanning speed differences

INTEN BAL balances the brightness of A and B time base trajectories for clear observation or photography in dual sweep mode

Working mode and operation process

1. Three core working modes

Mode name trigger condition applicable scenario key operation steps

Independent sweep mode (A or B works separately) – Normal trigger (AUTO TRIG pops up): The trigger signal must be ≥ 15Hz and the LEVEL must be correct

-Automatic trigger (AUTO TRIG pressed): Free operation at<15Hz or no trigger (baseline illuminated)

-Single trigger (A SINGL SWP pressed): Only 1 sweep frequency, A RESET is required to reset the regular time measurement of simple signals, non repetitive signal photography 1. Press the A or B button of MODE

2. Choose TRIGGERING SOURCE-COUPLING/SLOPE

3. Adjust LEVEL to stable display, press A RESET for standby in single mode

Dual sweep mode (A+B working simultaneously) A trigger source corresponds to the left vertical plugin, B trigger source corresponds to the right vertical plugin, and trigger parameters need to be set separately to observe two signals (or different scan speeds of the same signal) simultaneously. 1. Press the A+B button of MODE

2. Set the PLAY to ALT (fast scanning speed) or CHOP (slow scanning speed)

3. Adjust the Seconds/DIV and trigger parameters of A/B separately, and use INTERN BAL to balance the brightness

Delay sweep mode (B time base delay start): After triggering A time base, start B time base (or wait for triggering after B time base delay) signal local amplification, time difference measurement, pulse jitter measurement. 1. Press the A INTEN-B DLY’D button of MODE (in conjunction with A/B)

2. Set A Seconds/DIV (delay benchmark) and DELAY TIME MULT (delay multiplier)

3. Adjust the B Seconds/DIV (delayed sweep speed) to be faster than the A time base to avoid logic errors

2. Sweep frequency amplification operation (taking 100x amplification as an example)

Preparation for dual sweep mode: Press the A+B button, connect the left/right vertical plugs to the same signal, set A Seconds/DIV to 0.1ms/Div (display complete waveform);

Delay mode start: Press A INTEN-B DLY’D and use DELAY TIME MULT to locate the enhanced segment to the pulse that needs to be amplified;

B time base setting: B Seconds/DIV is set to 1 μ s/Div (1/100 of A scan speed), and at this time B time base displays a 100x amplified waveform of A time base enhancement segment;

Calculate magnification factor:

Magnification factor=B Seconds/DIV settings

A Seconds/DIV setting= 1×10 −60.1×10 −3=100

4、 Application scenarios and examples

1. Time difference measurement (interval between two pulses)

Signal access: The left/right vertical plug-in is connected to a signal containing two pulses, in dual sweep mode (A+B pressed), with Volts/Div set to 2 grid amplitudes;

A Time Base Setting: A Seconds/DIV is set to 0.2m/Div (displaying the multi grid distance between two pulses), and the trigger parameter is adjusted to stable display (using CHOP mode for slow scanning speed);

Delay mode start: Press A INTEN-B DLY’D, set B Seconds/DIV to 2 μ s/Div (1/100 of A scan speed), and strengthen the segment length by about 0.1 grid;

Delay positioning: DELAY TIME MULT first locates the rising edge of the first pulse (reading 1.31), and then locates the second pulse (reading 8.81);

Calculate time difference:

Time difference=(8.81-1.31) × 0.2ms=1.5ms

.

2. Pulse jitter measurement

Signal access: Left/right vertical plug-in access pulse signal, dual sweep frequency mode, Volts/Div set to 4 grid amplitude;

A Time Base Setting: A Seconds/DIV is set to display the complete waveform, and the trigger parameters are adjusted to stability;

Delay mode start: Press A INTEN-B DLY’D, DELAY TIME MULT locate the pulse to be tested, and set B Seconds/DIV to 0.2 μ s/Div (covering the pulse front);

Jitter calculation: observe the horizontal offset of the pulse in the B time base (example 0.5 grid),

Jitter=0.5 × 0.2 μ s=0.1 μ s

Electrical characteristics (core parameters)

Specific parameter accuracy/range for characteristic category

A time base scanning speed calibration range: 1 μ s/Div-5s/Div (21 levels); 100ns/Div 1 μ s/Div-1s/Div after 10x magnification: ± 3%; 2s/Div-5s/Div:±4%; Enlarged+1%

Non calibrated range: continuously adjustable, extending up to 12.5/s Div-

B time base scanning speed calibration range: 0.2 μ s/Div-0.5s/Div (20 levels) 1 μ s/Div-0.1s/Div: ± 3%; 0.2 μ s/Div, 0.5 μ s/Div, 0.2 s/Div, 0.5 s/Div: ± 4%

Delay characteristics: Delay multiple: 0.2-10.2 times A time base scanning speed (1 μ s-50s) 1 μ s/Div-0.5s/Div: ± 1%; 1s/Div-5s/Div:±2%

Inherent latency: ≤ 500ns-

Delay jitter: ≤ 1/20000 × 10x A time base scanning speed-

Trigger characteristic internal trigger (DC coupling): ≥ 0.4 grid (DC-1MHz); ≥ 0.6 grid (2MHz)-

External trigger (A time base): ≥ 200mV (DC-2MHz) Input RC: 1M Ω± 2%//70pF

Maximum safe input voltage: 350V (DC+peak AC)-

Amplifier mode deflection coefficient: 50mV/Div, 0.5V/Div ± 3%

Bandwidth: DC – ≥ 1MHz (AC coupling 50Hz – ≥ 1MHz)-

Non calibration range: ≥ 10:1 attenuation-

TEKTRONIX 5A22N Differential Amplifier

Operation Instructions (Section 1)

1. Instrument description

Positioning: High gain differential amplifier plug-in unit, used for 5100 series oscilloscopes, can directly couple input to achieve high sensitivity.

Core features:

Bandwidth: Maximum DC to 1MHz, bandwidth can be limited by HF-3dB (high frequency) and LF-3dB (low frequency) switches to improve signal-to-noise ratio;

Deflection coefficient: The knob skirt edge emits light and displays, supporting automatic scaling of 10X encoding probes;

Other: High common mode rejection ratio (CMRR), variable DC offset, suitable for displaying small signals at large DC levels.

2. Panel controls and interfaces (key functions)

Control/Interface Function Description

Display switch plugin working status (only valid for vertical cabin), when turned on, the knob skirt light is on

POSITION adjusts the trajectory position on the screen

HF -3dB/LF -3dB – HF -3dB: 1-3-10 sequence with 7 levels (0.1kHz-1MHz), reducing the upper bandwidth limit and improving signal-to-noise ratio

-LF-3dB: 1-10-100 sequence with 7 levels (DC-10kHz), limited to 2Hz during AC coupling; adjustable DC offset in DC OFFSET level

VOLTS/DIV – Calibration mode: 18 levels 1-2-5 sequence, 10 μ V/Div to 5V/Div (accuracy 2%)

-Variable gear: Non calibrated continuous adjustment, range extended to 12.5V/Div

DC OFFSET (COARSE/FINE) requires LF-3dB to be placed in the DC OFFSET mode to achieve display adjustment of small signals at large DC levels

STEP ATTEN DC BAL balanced input amplifier to reduce trajectory offset during VOLTS/DIV switching

Input coupling button (AC/DC/GND/PRE CHG) – AC: capacitive coupling (blocking DC); DC: direct coupling

-GND: Input ground (disconnect signal); PRE CHG: Press AC+GND to pre charge the coupling capacitor to the signal DC level

+/-Input interface BNC interface,+positive signal deflects upwards, – positive signal deflects downwards; Equipped with a 10X encoded probe ring

3. Basic operation steps

Installation and startup:

Insertion: Align the plug-in guide rail with the 5100 series module compartment (priority vertical compartment: center/left; X-Y operation can be inserted into the horizontal compartment), and the panel should be level with the oscilloscope;

Power on: Adjust the oscilloscope brightness to the lowest level → Power on → Preset time base (2ms/Div) and trigger (automatic trigger).

Initial setup:

Set PLAY to ON,+/- input coupling to DC+GND, POSITION and STEP ATTEN BAL to median, HF/LF-3dB to full bandwidth, VOLTS/DIV to 50mV/Div, and variable gear to CAL (clockwise to bottom).

Preheating and trajectory adjustment:

Preheating: Short term DC measurement for 5 minutes, long-term DC measurement for 15 minutes;

Adjust the brightness to normal, and the trajectory should be near the center of the scale. Use POSITION to move the trajectory to 2 grids below the centerline.

Example of signal measurement:

Single ended DC coupling:+input connected to 400mV peak to peak calibration signal → release+GND → display 4 grid square waves (bottom alignment step 3 reference line);

Single ended AC coupling: POSITION moves the trajectory from bottom to center → presses AC → the trajectory shifts downward by about 2 grids (to the average value);

Differential AC coupling:+/- input connected to dual input cable → – input set to AC → display straight line (common mode signal suppressed).

4. Key precautions

Input protection: The maximum voltage of the input FET gate is ± 12V (diode clamp), and the input fuse will melt when the signal source current exceeds 1/16A;

Pre charge (PRE CHG): When measuring AC signals containing DC components, first connect the AC+GND signal → wait for 1 second for charging → release GND to avoid damaging the signal source due to coupling capacitor charging current;

High impedance input: When VOLTS/DIV is in the 50mV-10 μ V range, removing the circuit board jumper can disconnect the 1M Ω ground resistor, achieving high impedance input (requiring the signal source to provide a DC path for FET gate current).

5. Electrical characteristics (core parameters)

Specific parameters of characteristics

Bandwidth (-3dB) – DC coupling: DC to ≥ 1MHz (independent of deflection coefficient)

-AC coupling: 2Hz to ≥ 1MHz

Common mode rejection ratio (CMRR) – DC coupling: 10 μ V/Div-0.1mV/Div range ≥ 100dB (DC-30kHz, 20Vp-p sine wave); 0.1V/Div-5V/Div mode ≥ 50dB (100Vp-p sine wave)

-AC coupling: ≥ 80dB at 5kHz and above, reduced to 50dB at 10Hz

DC offset range -10 μ V/Div-50mV/Div range: ± 0.5V

-100mV/Div-5V/Div mode: ± 50V

Input RC 1M Ω (± 0.1%) in parallel at approximately 47pF

Maximum input voltage DC coupling: 10V (DC+peak AC) (10 μ V-50mV range); 350V (DC+peak AC) (100mV-5V range)

-AC coupling: 350VDC+10V peak AC (10 μ V-50mV range, pre charged); 350V (DC+peak AC) (100mV-5V range)

Noise at full bandwidth (DC-1MHz) ≤ 20 μ V (25 Ω source resistance, tangent measurement)

Working principle (Section 2)

1. Overall block diagram path

Signal → Input coupling (AC/DC/GND) → Input attenuator (1X/100X, frequency compensation) → Pre amplifier (differential structure, floating ground power supply) → Low frequency limiting circuit (LF-3dB switching) → Gain switching stage (VOLTS/DIV control) → Offset generator (DC OFFSET) → Isolation stage (emitter follower) → Output amplifier (push-pull structure, POSITION adjustment) → Trigger signal amplifier (output to time base plugin, 0.25V/display panel).

2. Analysis of core circuit modules

Input attenuator:

Attenuation ratio: VOLTS/DIV 0.1V-5V range with 100X attenuation, 10 μ V-50mV range with 1X attenuation;

Features: Frequency compensation, maintaining 1M Ω//47pF input characteristics, balancing common mode signals through R132 (Atten DC CMR).

Pre amplifier:

Structure: Two identical operational amplifiers form a differential circuit (Q150A/B, Q190A/B, Q200A/B);

Floating power supply: composed of Q170/Q176 (constant current source) and VR173/175/176 (Zener transistor), it maintains the stability of the amplification device operating point and improves CMRR as the common mode signal changes;

Gate current compensation: Regulate R121/R127 to offset FET gate leakage current (≤ 100pA) and avoid high-sensitivity offset (such as 100pA × 1M Ω=100 μ V offset in 10 μ V/Div mode, which may cause trajectory offset screen).

DC offset generator:

Structure: Q240/Q244/Q246A/B form a voltage comparator, with VR251 (transistor) providing a reference voltage;

Function: By adjusting COARSE (R260) and FINE (R268), offset current is generated to cancel the DC component of the input signal, with a maximum cancellation of 0.5V.

Output amplifier:

Structure: Push pull amplifiers Q348/Q352, R351 (GAIN) adjust the total gain to match the requirements of the host;

Position adjustment: Q360/Q362 (positioning current drive), R360 (POSITION) changes the current to adjust the static position of the CRT beam.

Calibration (Section 3)

1. Calibration prerequisites and preparations

Applicable scenarios: After instrument maintenance, long-term use (component aging) leads to accuracy deviation;

Environmental requirements: Temperature of 20-30 ℃, preheating for 20 minutes;

Equipment disassembly: Remove the left protective cover of 5A22N and the left panel of 5100 series oscilloscope (or use plug-in extender 067-0645-00);

Initial settings: Set the 5A22N control to POSITION median LF-3dB=1Hz、HF-3dB=1MHz、VOLTS/DIV=50mV、 Variable gear=CAL,+/- input=DC+GND, STEP ATTEN BAL median; The 5B10N time base is set to automatic triggering,+slope, and AC coupling.

2. Required testing equipment (including accessories)

Specific requirements/model examples for equipment types

Oscilloscope System 5100 Series (including 5B10N Time Base Plugin)

Constant amplitude sine wave generator frequency 2Hz-1MHz, output 0.5V-40Vp-p (such as General Radio 1310-B)

Standard amplitude calibrator 1kHz square wave, output 5mV-50V, accuracy ± 0.25% (recommended 067-0502-01)

Accessories – Coaxial Line: 50 Ω, 42 inches, BNC(012-0057-01)

-Dual input cable: matching signal path, BNC(067-0525-00)

-1000:1 voltage divider: accuracy ± 0.2% (067-0529-00)

-Input RC Normalizer: 1M Ω× 47pF (067-0541-00)

-Serial terminal: 50 Ω, accuracy ± 2% (011-0049-01)

3. Key Calibration Steps (Core 8 Steps)

Step attenuator balance:

R292 (AC STEP ATTEN BAL): Switch between VOLTS/DIV 50mV-0.1V to minimize trajectory offset;

Adjust R318 (VAR BAL): Shift the variable gear from CLOCKWISE to COUNTERCLOCKWISE to minimize trajectory deviation;

Adjust R250 (COARSE DC BAL): Set LF-3dB to DC, switch VOLTS/DIV 50mV-0.1V, and minimize trajectory offset.

Gate current regulation:

+Input to 50 Ω terminal → LF-3dB=DC → Release+GND → Switch+AC, adjust R121 (+GATE CURRENT), minimize trajectory offset;

-Input to 50 Ω terminal → press+GND → release – GND → switch – AC, adjust R127 (- GATE CURRENT), minimize trajectory deviation.

Attenuator DC common mode rejection:

Release+/- GND → VOLTS/DIV=0.1V →+/- Input through dual cables connected to a 50V square wave (calibrator) → Adjust R132 (ATT DC CMR) to display the minimum amplitude.

Input compensation:

-GND pressed ->VOLTS/DIV=50mV ->+input connected to 0.5V square wave (normalized by RC) ->C118 adjusted (Atten Time Constant), with the best square wave front;

Similarly, input C148, C145, C142.

Amplifier gain calibration:

VOLTS/DIV=10mV →+input connected to 50mV square wave → adjust R351 (GAIN), display amplitude exactly 5 grids;

Turn the variable gear to COUNTERCLOCKWISE, with a display amplitude of<2 grids, and then turn it back to CAL.

VOLTS/DIV accuracy check:

VOLTS/DIV=5V →+input connected to 20V square wave (through 1000:1 voltage divider X1 gear) → gradually decrease VOLTS/DIV, synchronously adjust the calibrator output, ensure display of 4-5 grids, accuracy ± 2%;

VOLTS/DIV=5mV gear → voltage divider set X1000 → calibrator output 20V → HF-3dB=10kHz → repeat the above checks.

Common mode rejection ratio (CMRR) calibration:

Release – GND → VOLTS/DIV=10mV →+/- input connected to 20Vp-p, 50kHz sine wave → adjust C160 (CMR 2), display minimum;

VOLTS/DIV=50 μ V → Time base=10 μ s/Div → Adjust C220 (CMR 1), display minimum;

LF-3dB=0.1kHz → switch to C210 (CMR 3), display minimum, repeat until there is no interaction effect.

Bandwidth calibration:

-GND pressed → VOLTS/DIV=1mV → LF-3dB=DC → Time base=1ms/Div →+input connected to 1kHz, 8-grid sine wave → Generator output 1MHz → C330 adjusted, display amplitude reduced to 5.6 grid (-3dB point).

Drawings and Parts List (Section 4)

1. Symbols and reference identification rules

Component symbol: Following ANSI Y32.2-1970 standard, logical symbol follows MIL-STD-806B (positive logic);

Reference identification prefixes: C=capacitor, R=resistor, Q=transistor, CR=diode, F=fuse, J=fixed connector, S=switch, VR=voltage regulator (transistor), etc.

2. Core Parts List (Example)

Part Type Reference Identification Tektronix Part Number Specification Description

Capacitor C103 283-0002-00 0.01pF, ceramic, 500V

Capacitor C133 283-0626-00 1800pF, mica, 5%

Resistance R120 322-0481-07 1M Ω, 1/4W, 1/10%

Resistance R121 311-1223-00 250 Ω, variable

Transistors Q150A/B 151-1027-00 silicon FET, replaceable with D/2N4394 or FD1392

Transistors Q103/Q105 151-0347-00 silicon NPN, replaceable with 2N5551

Diode VR138 152-0520-00 Zener diode, 1W, 12V, replaceable with UZ8712 or HW12B

Switch A10 (LF-3dB) 105-0310-00 cam switch

Switch S280 (VOLTS/DIV) 105-0309-00 cam switch

Circuit board A1 670-1894-00 main circuit board component

Tektronix 5440 oscilloscope

Overview of Instrument Core

(1) Hardware structure

Plugin compartment: There are a total of 3 compartments that can accommodate 5000 series plugins (without N suffix plugins supporting display readings), 2 vertical compartments (left and middle) for amplifier plugins, and 1 horizontal compartment (right) for time base plugins. The combination of plugins determines the functionality of the measurement system.

Key controls:

Display related: INTENSITY adjusts the brightness of the trajectory, READOUT INTENS only adjusts the brightness of the reading part (the reading system fails when counterclockwise to the bottom), FOCUS controls for clear display, and BEAM FINDER compresses the trajectory to the scale range.

Power supply and calibration: The power switch (POWER) controls the power on/off, and the internal calibrator (CALIBRATOR LOOP) provides a square wave signal with a voltage of 400mV (± 1%) and a current of 4mA (± 1%), with a frequency of twice the power supply frequency, for calibration and probe compensation.

External interface: EXT INTENSITY INPUT interface receives Z-axis modulation signals (DC coupling,+5V enhanced brightness, -5V reduced brightness, maximum safe input ± 50V, frequency range DC to 2MHz).

(2) Core functions

Display mode:

Alternate mode: The time base plugin display switch pops up and switches between the activated plugin/channel with each CRT scan, suitable for high-frequency signals.

Chop mode: When the time base plugin display switch is pressed, it electronically switches between channels at a rate of 100kHz, suitable for displaying low-frequency signals or single event phenomena.

X-Y operation: Install 5A series amplifiers or 5B series time base plugins with amplifier channels in the horizontal cabin to receive X signals, and 5A series amplifiers in the vertical cabin to receive Y signals, achieving signal comparison display.

Grating display: Both the left vertical cabin and the horizontal cabin are equipped with 5B series time base plugins. The scanning speed of the vertical cabin is slower than that of the horizontal cabin, and brightness modulation is achieved through EXT INTENSITY INPUT, which can simulate TV display.

Reading System: Only supports 5400 series plugins, displaying alphanumeric information in real-time with analog waveforms on CRT. Each plugin’s reading occupies a fixed position (channel 1 is indexed at the top, channel 2 is indexed at the bottom), displaying up to 6 readings (option 3 can select 8 readings). The reading interruption waveform display is only about 20 microseconds/character.

Operation Guide

(1) First operation process (19 steps in total, with the following key steps)

Plug in preparation: Install 5A series amplifier plugs in the left/middle vertical cabin and 5B series time base plugs in the horizontal cabin.

Power connection: After confirming the operating voltage, turn off the power switch and connect a power source that meets the voltage/frequency requirements.

Initial setup:

Amplifier plugin: Display on, center position, CH1 Volts/Div set as needed, CH1 Variable Volts/Div clockwise to the end (Cal), CH1 Input Coupling set to DC, mode set to CH1.

Time base plugin: Display alternately (button pops up), center position, Main Sec/Div set to 5ms, Variable Seconds/Div clockwise to the end (Cal), Swp Mag turned off (button pops up), Main Trig Level counterclockwise to the end, trigger source selected to the left (or center, if the amplifier is in the middle compartment), coupled with Auto Trig, AC Couple,+Slope, mode set to Main Sweep.

Calibration check: Connect the probe/test line to the calibrator, adjust the trigger level to obtain stable display, check the waveform amplitude (4 divisions) and cycle (6 complete cycles, 5 cycles for 50Hz power supply), and recalibrate if abnormal.

(2) Basic measurement methods

Calculation formula/explanation for key steps of measurement type

AC peak to peak voltage: 1. The vertical plug-in input coupling is set to Gnd, and AC is set after receiving the signal; 2. Volts/Div is set to display 5-6 vertical divisions, and Variable Volts/Div is set to Cal; 3. Adjust the trigger to obtain stable display, and measure the vertical division of peak values; 4. Result=Division value × Volts/Div × Probe attenuation ratio (if any) Example: 4.6 Division value × 5V/Div=23V

DC instantaneous voltage: 1. The vertical plug-in input coupling is set to Gnd, and the trajectory is positioned to the reference line (such as the bottom part degree, negative voltage is used at the top); 2. After receiving the signal, set the DC and measure the vertical division between the reference line and the measurement point; 3. Result=division value x Volts/Div x probe attenuation ratio (if any), polarity determined by waveform position (+input and waveform is positive on the reference line) Example: 4.6 division x 2V/Div=+9.2V

Time cycle 1. Connect the signal, select AC/DC coupling, set Volts/Div to display 4 divisions; 2. Adjust the trigger to obtain stable display, set Sec/Div to 1 cycle display<8 divisions; 3. Measure the horizontal division of two points (Variable Sec/Div at Cal); 4. Result=Division value x Sec/Div Example: 5 divisions x 0.1ms/Div=0.5ms

Frequency 1. Obtain the period (T) by measuring the time period method; 2. Frequency=1/T Example: Period 0.5ms, Frequency=1/0.5ms=2kHz

Rising time (10% -90% point) 1. Connect the signal, set Volts/Div and Variable to display 5 vertical divisions; 2. Adjust the trigger to obtain stable display, set Sec/Div to 10% -90% point display<8 divisions; 3. Measure the horizontal division of two points; 4. Result=Division value x Sec/Div Example: 4 divisions x 1 μ s/Div=4 μ s

Specification parameters

1: Vertical amplifier specifications

Additional information on characteristic performance requirements

Bandwidth (6-degree reference) DC to at least 85MHz (067-0680-00 calibration fixture); DC to at least 50MHz (calibrated 5A48)-

Rise time (6 divisions reference) 7ns or less (calibrated 5A48)-

Distortion (6-degree reference) 5% or less (067-0680-00 calibration fixture); 4% or less (calibrated 5A48)-

The influence of position on distortion ± step response signal deviation does not exceed ± 5% (trajectory deviation from the center of the scale does not exceed 1 division)-

Within ± 0.5 divisions of the center of the vertical center scale-

Delay line length 140ns-

Chopping rate 50kHz (+50% -30%), conducting in 3 μ s and turning off in 2 μ s-

Alternating rate: scan every two times-

Table 2: Specifications of Horizontal Amplifier and Z-axis Amplifier

Performance requirements for amplifier type characteristics

Horizontal amplifier bandwidth DC to at least 2MHz (8-division signal reference); At least 20kHz at the low frequency end

The Z-axis amplifier inputs a voltage of+5V to switch the CRT beam from off to on; -5V switches the beam from on to off

Available frequency range DC to 2MHz

Input impedance (resistance) 10k Ω

Table 3: Power, Environment, and Physical Specifications

Category Characteristics Performance Requirements

Power input voltage (RMS) nominal 100V, 110V, 120V, 200V

Input frequency adapted to standard power frequency

Maximum 100W at 120V AC and 60Hz input power

Fuse 120V AC with 1.25A slow melting; 240V AC with 0.7A slow melting

Environmental working temperature: 0 ° C to+50 ° C

Storage temperature -40 ° C to+70 ° C

Working altitude up to 15000 feet

Storage altitude up to 50000 feet

Physical weight 25lbs (11kg)

Panel and shell anodized aluminum panel (gray vinyl coated frame), blue vinyl coated shell

Scale dial 8 × 10 divisions, 1.22cm/division, standard white internal scale line, optional black

Installation and maintenance

(1) Rack installation

Requirement: Suitable for 19 inch standard racks (Universal, EIA, RETMA, Western Electric hole positions), with a minimum vertical space of 5-1/4 inches and an additional 1/4 inch heat dissipation space above and below; Front rail spacing ≥ 17-5/8 inches (unthreaded) or 17-3/4 inches (tapped); The gap between the rear and the rack enclosure is ≥ 2 inches.

Sliding rail installation: The sliding rail is divided into left and right components (marked LH/RH), with the fixed section installed on the front and rear rails of the rack, the chassis section pre installed with instruments, and the middle section connecting the two; During installation, it is necessary to align horizontally to avoid exchanging left and right (which may cause the safety lock to fail and cause the instrument to slide). The front panel needs to be fixed with 10-32 screws (the rack needs to correspond to the hole position).

Maintenance: The slide rail does not require lubrication, and the dark coating on the sliding parts is permanently lubricated.

(2) Plugin installation and maintenance

Installation: Align the upper and lower slots of the plug-in with the cabin guide rail, and push it into the lock; It can be plugged and unplugged with power, without filling all cabins, only installing the required measuring plugs is needed.

Calibration: After the display unit is calibrated according to the instructions, the vertical/horizontal gain is standardized. The plug-in can be interchanged between cabins without the need for readjustment, but the basic calibration of the plug-in itself needs to be checked to ensure measurement accuracy (refer to the plug-in manual).

(3) Safety regulations

Maintenance safety: Only qualified personnel are allowed to carry out repairs, and individual repairs are prohibited (emergency personnel must be provided); Live maintenance should avoid touching exposed connections/components, and disconnect the power supply before dismantling panels, welding, or replacing components.

Power safety: The power supply must meet the RMS voltage between phase lines and between phase lines and ground ≤ 250V, and the grounding conductor of the power line must be reliably grounded.

Performance check

(1) Testing equipment requirements (key equipment as follows)

Equipment Name Performance Requirements Application Scenarios

DC voltmeter range 0-200V (accuracy 0.1%); 0-3000V (accuracy 1%) low/high voltage power supply inspection and adjustment

Calibration generator amplitude calibration 10mV-1V (accuracy ± 0.25%, 1M Ω load), square wave output gain inspection and adjustment

Timing generator outputs 5ns and 10ns markers (accuracy ± 1%) for scanning timing inspection (5ns, 10ns)

5A48 amplifier plug-in bandwidth DC to 500MHz, display mode CH1 vertical/horizontal system adjustment

5B42 time base plugin scanning speed of at least 10ns/div scanning timing inspection and adjustment

(2) Key inspection items

Trajectory alignment: Horizontal trajectories are aligned with the center horizontal scale line, and vertical trajectories are aligned with the center vertical scale line, with an error of ≤ 0.1 divisions.

Geometric shape: Trajectory curvature/inclination ≤ 0.1 divisions, angle between vertical and horizontal trajectories 90 °± 0.7 °.

Vertical performance:

Gain: Input 1kHz square wave, display 5V reference signal, vertical deflection of 5 divisions ± 0.15 divisions (± 3%).

Bandwidth: Input a 50kHz sine wave, display 6 divisions, increase the frequency until the amplitude drops to 4.2 divisions, and the frequency needs to be ≥ 50MHz (5A48 plugin).

Horizontal performance:

Gain: Input 1kHz square wave, display 5V reference signal, horizontal deviation of 5 divisions ± 0.15 divisions.

Bandwidth: Input a 50kHz sine wave, display 6 divisions, increase the frequency until the amplitude drops to 4.2 divisions, and the frequency needs to be ≥ 2MHz.

Reading system: In dual track mode, readings are displayed at the top/bottom of the CRT without overlap, corresponding to Volts/Div and Sec/Div settings; When CAL controls counterclockwise rotation, the “>” symbol is displayed on the left side of the reading.

TOSHIBA MULTIFUNCTIONAL DIGITAL SYSTEMS

Software License Agreement

Core licensing rules

License Scope: Users are only allowed to use one copy of the software on a single system CPU (device where the software is installed), and can only copy it for usage purposes. The copy must comply with this agreement.

Prohibited behavior: Do not modify, decompile, disassemble or reverse engineer software; Do not sublicense, rent, transfer licenses or software.

Intellectual Property: The software (including fonts and documentation) is proprietary to Toshiba Tec Corporation (TTEC) and its suppliers, protected by copyright laws and international treaties. Users have no intellectual property rights and are licensed as passive code.

Agreement Term and Termination

Effective condition: Installing or using the software is considered acceptance of the terms.

Termination situation: TTEC termination, or user breach (such as violation of prohibited behavior); After termination, all copies of software and documentation must be destroyed; Users can voluntarily terminate (destroy software and copies).

Disclaimer and Limitation of Liability

Disclaimer: The software is provided as is (AS IS) without any express or implied warranties (including merchantability, fitness for a particular purpose, etc.); The cost of repairing/correcting software defects shall be borne by the user.

Limitation of Liability: TTEC and its suppliers shall not be liable for indirect losses (such as loss of profits, data loss), unless personal injury/death is caused by the fault of TTEC or its suppliers.

Government restrictions on rights: The use of technology by the US government must comply with the Technical Data and Computer Software Rights Clause (such as 252.227-7013, 52.227-19), and the contractor is Toshiba Tiger Co., Ltd. from Japan.

Basic information (trademark, copyright, manual system)

Trademark and Copyright

Trademarks: Windows series (Microsoft), Apple series (Apple), PostScript (Adobe), TopAccess (TTEC), etc. are corresponding company trademarks.

Copyright: © 2007 TOSHIBA TEC CORPORATION, Unauthorized reproduction of manuals is prohibited and patent liability is not assumed.

Manual system: Multiple manuals are provided, and users can choose according to their needs, as shown in the following table:

Manual Name Core Content

Quick Start Guide: Device Initial Setup, Accessories (Manual, CD-ROM) Instructions

Operator’s Manual for Basic Functions Basic Functions (with a focus on copying) Usage and Safety Precautions

Functions and settings under the “User Functions” button in the User Functions Guide control panel

Color Guide (color models only) Color related functions (density adjustment, color adjustment, etc.) and basic knowledge of color

TopAccess Guide: This document manages network functions (scanning, job management, etc.) through TopAccess

Network Administration Guide Network Server Setup Guide, Network Troubleshooting (for administrators)

Printing Guide: Windows/Mac/UNIX System Printing Client Software Installation and Printing Operations

Scanning Guide Operation Instructions

The e-Filing Guide uses TWAIN driver, File Downloader, and other operations to perform e-Filing functions

Network Fax Guide network fax function (client sends fax/Internet fax)

User Management Guide: Department Management, User Management Settings, Scan to Email Authentication

TopAccess Overview and End User Mode

1. TopAccess Overview

Definition: A web-based homework and device management tool that supports accessing device information through the network, divided into user mode (regular user) and administrator mode (administrator configuration).

Access prerequisite: The device needs to be connected to the network and configured with TCP/IP settings.

Browser support:

The operating system supports browser versions

Windows Internet Explorer 5.5 SP2+/Firefox 1.5.0.4+(IPv6 requires IE 7.0+)

Macintosh Safari 2.0+/Firefox 1.5.0.4+

UNIX Firefox 1.5.0.4+

Access method: Enter the URL (http://<IP address>or http://<device name>), such as http://10.10.70.105 .

2. Core functions of user mode

(1) View device status (Device Tab Page)

Device information: Display device name, location, model, storage space (such as Save as File space, e-Filing space, fax sending and receiving space), contact information, administrator message, alert (error red/warning yellow).

Option status: Display the installation status of optional units (binders, punching units, fax units, etc.).

Paper status: Display the paper size, type, capacity, and consumption status of each paper box (such as “Near Empty”/”Empty”).

Equipment status indicator light: indicates faults through icons (such as paper jam, paper box open, toner depletion, etc.), which should be resolved by referring to the “Basic Function Operation Manual”.

(2) Managing Jobs

Print homework:

Display: View user submitted print jobs (username, date and time, type, paper size, etc.), refresh the list, and sort by header.

Operation: Delete (select 1 at a time, private print jobs need to be deleted by the administrator), Release (select 1 at a time, private jobs cannot be released).

Fax/Internet fax operation:

Display: View fax transmission jobs (file number, destination, date and time, page number, etc.), which can be refreshed and sorted.

Operation: Delete (select one at a time).

Scan homework:

Display: View scan jobs (target/file name, agent, date and time, page count, status), which can be refreshed and sorted.

Operation: Delete (select one at a time).

(3) Viewing Job Logs

Log type: Each log can store up to 100 entries, displayed in reverse chronological order. If exceeded, the earliest record will be deleted

Print log: username, document name, date and time, type, paper size, page count, number of copies.

Transmission log: serial number, file number, date and time, transmission duration (displayed as “59:59” after 1 hour), page count, destination, department code, mode, status, route.

Receiving logs: serial number, file number, date and time, receiving duration, page count, sender, department code, mode, status, line.

Scan logs: target/file name, username, agent, date and time, page count, mode (6-digit code, including job type/transfer type, etc.), status.

(4) Registering from TopAccess

Template management:

Private template group: up to 200, can set group name, owner, email notification, supports password protection (5 digits); Resetting the group will delete all templates within the group.

Private templates: Up to 60 per group, with the option to select agents (copy/fax/scan, etc., scan up to 2 agents), set parameters such as panel, destination, format, etc., and support password protection.

Public template: Only administrators can create/maintain it, users can view it.

Address book management:

Contact person: manually add/edit/delete (name+email/fax number required), or search and add from LDAP server; Fax parameters can be set (such as ECM, line selection).

Group: Create/edit/delete groups (including multiple contacts) for easy bulk sending.

Email management (requires installation of fax unit):

Type: Confidential email (deleted after a single extraction), Billboard email (multiple extractions), Forwarding email (forwarding to other devices/network folders/email/e-filing).

Operation: Create/edit/delete up to 300 email addresses, set passwords, notifications, storage paths, etc.

(5) View counters (Managing Counters)

Total counter: View the total number of pages copied/printed (small/large paper) and scanned (divided into full-color/two-color/black).

Department counter: After entering the department code, view the counter for a specific department. You can click on the department name to view detailed data.

TopAccess Administrator Mode

1. Overview of Access and Core Functions

Access method: After entering TopAccess, click on “Administration” and enter the administrator password (default “123456”) to log in.

Core functions: settings (devices/networks/printing services, etc.), maintenance (software updates/data backups), registration (public templates/fax forwarding), user and department management, viewing message logs.

2. Key Function Details

(1) Setting up from TopAccess

Device settings: Configure device name, location, administrator password (6-10 alphanumeric characters), energy-saving time (automatic clearing/sleep/shutdown), date and time, TopAccess language, and session timeout (5-999 minutes).

Network settings: Configure TCP/IP (static/dynamic IP), IPv6, IPX/SPX, AppleTalk, LDAP, DNS, SMTP/POP3, FTP, SNMP, SSL certificates, etc.

Copy settings: default color mode, original mode, exposure, maximum number of copies (9/99/999/9999), etc.

Fax settings (requiring installation of fax unit): Terminal ID, fax number, receiving mode, resolution, ECM, etc.

Printing service settings: Enable/disable Raw TCP (port 9100), LPD (port 515), IPP, FTP, NetWare, Email printing, configure port numbers, authentication, etc.

(2) Maintaining from TopAccess

Software management: Upload client software (drivers, PPD files, etc.), delete software (except for Point and Print drivers).

Data backup and recovery: Backup address book/template/email data (generate backup files), restore data from backup files.

Log management: Export logs (CSV format, including print/fax/scan logs), clear logs.

Directory service: Register LDAP servers (up to multiple), configure server IP, ports, and authentication methods.

Device restart: Restart the device (ensuring that no jobs are running).

(3) User and Department Management

Department management:

Function: Register/modify/delete department codes (up to multiple), set department names, output restrictions (full-color/black), clear department counters.

Note: The default ‘Undefined’ department cannot be deleted and is used to count invalid jobs.

User management:

Authentication methods: Supports Windows domain authentication, LDAP authentication, and MFP local authentication (up to 10000 users).

User operation: Create/edit/delete users, set usernames, passwords (local authentication), departments, permission restrictions, reset user counters.

(4) Troubleshooting

Error code: Provide error codes and solutions by job type (print/transmit/scan), for example:

402F: 1200 dpi print job requires additional memory, it is recommended to change to 600 dpi.

0011: Cardboard, the paper needs to be cleared.

1C65: SMTP address not set, administrator needs to configure SMTP server.

Other important notes

Optional component dependencies: Some features require the installation of optional components, such as fax unit for fax function and scanner kit for scanning to email.

Security precautions: Enabling SSL requires importing a certificate (self signed or CA certificate); SMTP/POP3/LDAP authentication requires correct configuration of username and password.

Data limitation: Address book import/export supports CSV format; Up to 100 logs can be stored; Up to 300 email addresses; The maximum number of private template groups is 200.

TOSHIBA e-STUDIO 7516AC Color Multifunctional Printer

Product basic information

Positioning and Model: The Toshiba e-STUDIO 7516AC series is a color multifunctional printer designed for large workgroups, consisting of three models – e-STUDIO 5516AC, e-STUDIO 6516AC, and e-STUDIO 7516AC. Its core goal is to simplify complex office tasks through customized features, balancing efficiency, safety, and environmental requirements.

Core function: Integrated with four basic functions of copying, printing, scanning, and faxing, supporting high-capacity and high-speed document processing, while also having the ability to customize UI and automate workflow, adapting to personalized office scenarios of different enterprises.

Core performance parameters

Specific parameters of performance category (in order of e-studIO5516AC/6516AC/7516AC)

Printing/copying speed color: 55 PPM/65 PPM/75 PPM; Black and White: 65 PPM/75 PPM/85 PPM

First print output time color: 6.4 seconds/6.4 seconds/5.4 seconds; Black and white: 5.2 seconds/4.5 seconds/4.1 seconds

Resolution copying: 600 × 600 dpi; Printing: 600 × 600 dpi (8-bit), 1200 × 1200 dpi (color/2-digit), 3600 × 1200 dpi (black and white/with smoothing, PS3 only)

Maximum monthly copy volume of 480K pages/540K pages/600K pages

Preheating time is about 20 seconds

Scanning speed dual scan document feeder (DSDF): up to 240 IPM for double-sided and up to 120 IPM for single-sided (black and white/color compatible)

Color toner capacity (CMY): 39200 pages (5% coverage); Black (K): 106600 pages (5% coverage)

Power supply and power consumption: 120V, 50/60Hz, 16A; Maximum power consumption: 2.0kW (120V); Super sleep mode: 0.6W

Hardware and operational configuration

Core hardware: Equipped with Intel Atom 1.75GHz dual core processor, 4GB memory and 320GB self encrypting hard drive (SED), the hardware has strong performance and can smoothly run embedded solutions and third-party applications, while ensuring data storage security.

Operation display screen: It adopts a 10.1-inch color WSVGA tiltable touch screen, built-in embedded web browser, and operation logic similar to a tablet; Support customizing the homepage taskbar by department, displaying only high-frequency functions to reduce operational redundancy, and featuring accessible designs such as tilted panels and universal paper tray handles.

Paper processing capability

Capacity configuration: The standard 4-drawer design can accommodate 2280 sheets of paper, while the serial drawer version has a standard capacity of 3520 sheets; The maximum capacity can be expanded to 4780 sheets (4 drawers) or 6020 sheets (series drawers), and the MP2502B 2500 large capacity feeder (only supports LT size) can be optionally selected to reduce frequent paper feeding frequency.

Support range: Paper sizes ranging from 3.9 “x 5.8” to 13 “x 19” regular sizes, 12 “x 47” banners, and envelopes; The paper weight range is 16 pounds Bond to 140 pounds Index (standard drawer), 16 pounds Bond to 110 pounds Cover (bypass feed), suitable for various document printing needs.

Featured features and connectivity

Workflow optimization function

Elevate function: It can customize automated workflows based on enterprise business processes, simplifying multi-step operations (such as scanning, converting formats, uploading to cloud storage) into “one click execution”, reducing manual operations and paper consumption, lowering costs, and improving efficiency.

Print Around: When a printing task is stalled due to paper size, type, or toner issues, other tasks are allowed to print first to avoid printing queue congestion and ensure smooth flow in high load scenarios.

Scan and fax enhancement: supports scan preview (viewing, rotating, and adjusting scanned documents on the touch screen), fax preview (viewing received faxes before deciding whether to print, saving consumables); Scanning can be directly saved in Office formats such as DOCX, XLSX (with embedded OCR enabler).

Connection and compatibility

Mobile and wireless connectivity: Supports AirPrint ® (Apple devices) Mopria ® (Android devices) Wi-Fi Direct, Paired with Toshiba’s exclusive e-BRIDGE Print&Capture application (available for download on iOS/Android), it enables direct printing and scanning of documents on mobile phones/tablets, and sending them back to mobile devices.

Cloud service integration: Through the e-BRIDGE Plus series of applications, it supports OneDrive access ®  for Business、SharePoint ®  Online、Exchange Online、Google Drive ™、 DropBox ®  Wait for cloud storage to print documents, or scan documents and upload them directly to the cloud platform to achieve cross device document sharing.

System and protocol compatibility: compatible with Windows ® (8.1/10/Server 2012 and above) Macintosh ® (macOS X 10.7.4 and above) Unix ®、 Linux ®  System; Support printing protocols such as SMB, LPR/LPD, IPP, Port 9100, etc., to meet different office network environments.

Safety and Environmental Protection Standards

Security protection system

Data Security: Comes standard with a 320GB self encrypting hard drive (SED), supporting automatic data invalidation (ADI) and data overwrite functions to prevent data leakage after the hard drive is stolen or the device is scrapped; Optional FIPS 140-2 certified SED, compliant with government level security encryption standards; Supports IPsec encryption protocols (IKEv1/IKEv2) to ensure secure data transmission between devices and networks.

Access control: Supports multi-dimensional authentication (device authentication, Windows domain authentication, LDAP server authentication, card/NFC authentication), MAC/IP address filtering (10 groups each), role-based access control (RBAC), only authorized users can operate core functions; Simultaneously supporting secure PDF and firmware digital signatures to prevent malicious software attacks and unauthorized firmware tampering.

Compliance certification: Through HCD-PP certification and CC certification (ISO/IEC15408), it complies with internationally recognized information security assessment standards and is suitable for industries sensitive to data security, such as finance and government.

environmental performance

Certification standard: Compliant with ENERGY STAR ®  V3.0 certification, EPEAT Gold registration, using RoHS compliant materials, and using recycled plastic for the body to reduce environmental impact.

Energy saving design: Supports super sleep mode (with a power consumption of only 0.6W), low monthly average energy consumption (TEC value), and reduces operating electricity costs; Equipped with e-Bridge Plus green information function, it can display the company’s environmental contribution data (such as reduced carbon emissions) on the touch screen, guiding employees to use the equipment efficiently.

Optional accessories

Accessory category, model, and function description

GR1330 accessory tray for auxiliary operation accessories, used to place small operating tools or consumables

GR9000 Bluetooth keyboard simplifies device side text input operations

GR1340 10 key numeric keypad improves numerical input efficiency

Binding and output accessories MJ1111B 50 page console stapler, supporting single/multi page stapling binding

MJ1112B 50 page saddle stitch stapler, supporting saddle stitch binding and folding of picture books and manual documents

MJ6106N punching unit (compatible with MJ1111B/MJ112B), supports document punching processing

KA6551 side paper tray provides additional document output channels to avoid confusion with the main tray

Connect and secure accessories GD1370N fax unit/second fax line, expand fax function or add fax line redundancy

GN4020 wireless LAN/Bluetooth module, enabling wireless connection of devices and adaptation to Bluetooth peripherals

GE1230 FIPS 140-2 certified self encrypting hard drive (SED) meets high security level data storage requirements

GP1080 IPsec Security enabler, activates device IPsec encryption function

Function extension accessory GS1080NODE embedded OCR enabler (authorized by seat), supporting the conversion of scanned documents into editable Office formats

GS1090NODE multi workstation printing enabler (authorized by seat), supports users to obtain printing tasks on any device with card authentication

Paper expansion accessory MP2502B 2500 large capacity feeder (only supports LT size), significantly increasing paper reserve capacity

Troubleshooting and Maintenance

Fault code system

Indoor unit fault codes: covering communication faults (such as E03: indoor remote control communication interruption, E04: indoor outdoor communication interruption), sensor faults (such as F01: TCJ sensor open/short circuit, F10: TA sensor fault), hardware faults (such as P10: indoor overflow, P12: DC fan fault), each code corresponds to a clear troubleshooting direction (such as checking line connections, sensor resistance, hardware components).

Outdoor unit fault codes: including communication faults (E06: indoor unit disconnection, E23: outdoor outdoor communication interruption), abnormal pressure/temperature (P03: high exhaust temperature, P20: high pressure protection activated), compressor faults (H01: compressor overcurrent, H02: compressor lock), which need to be checked in conjunction with the 7-segment display on the external unit interface board and manual steps.

Test run operation

Wired remote control (RBC-AMT series): Press and hold the 【 TEST 】 button for more than 4 seconds to enter the test mode, press 【 MODE 】 to switch between ‘cooling/heating’, and the test will automatically exit after 60 minutes. During this period, the temperature cannot be adjusted, and the fault detection will take effect normally.

Wireless remote control: After turning on, wait for 1-5 minutes (5 minutes for the first power on), press [ON/OFF] to start, select “cooling/heating” for [MODE], select “HIGH” for [FAN], activate the test through a specific temperature setting sequence (such as cooling: 62 ° F → 64 ° F → 62 ° F), and the indicator light flashes for 10 seconds before starting.

Regular maintenance checklist

Daily maintenance: Clean the filter screen weekly (standard filter screen can be washed with water), check the paper capacity indicator, check the remaining consumables (toner, toner cartridge) monthly, and confirm that the safety lock and certification functions are normal.

Quarterly maintenance: Clean the scanning platform and feeder rollers, check network connection stability, test IPsec and data encryption functions; Every year, professionals inspect the health of SED hard drives, calibrate sensors (TA/TC1/TC2), and check the operating status of environmental protection modes.

TOSHIBA e-STUDIO 7516AC Series Color Multifunctional Printer

Product basic information

Product Series and Positioning: The Toshiba e-STUDIO 7516AC series is a color multifunctional printer designed specifically for large workgroups. It includes three models: e-STUDIO 5516AC, e-STUDIO 6516AC, and e-STUDIO 7516AC. The core goal is to simplify office processes, improve efficiency, and balance safety and environmental protection through advanced features.

Core function coverage: integrating four major functions of copying, printing, scanning, and faxing, supporting diverse document processing needs, and possessing the ability to customize UI and automate workflow, adapting to personalized office scenarios of different enterprises.

Core Performance Parameters (Table Display)

Specific parameters of performance category (in order of e-studIO5516AC/6516AC/7516AC)

Printing/copying speed color: 55 PPM/65 PPM/75 PPM; Black and White: 65 PPM/75 PPM/85 PPM

First print output time color: 6.4 seconds/6.4 seconds/5.4 seconds; Black and white: 5.2 seconds/4.5 seconds/4.1 seconds

Resolution copying: 600 × 600 dpi; Printing: 600 × 600 dpi (8-bit), 1200 × 1200 dpi (color/2-digit), 3600 × 1200 dpi (black and white/with smoothing, PS3 only)

Maximum monthly copy volume of 480K pages/540K pages/600K pages

Preheating time is about 20 seconds

Scanning speed dual scan document feeder (DSDF): up to 240 IPM for double-sided and up to 120 IPM for single-sided (black and white/color compatible)

Color toner capacity (CMY): 39200 pages (5% coverage); Black (K): 106600 pages (5% coverage)

Hardware and operational configuration

Core hardware: Equipped with Intel Atom 1.75GHz dual core processor, 4GB memory and 320GB self encrypting hard drive (SED), providing hardware foundation for high-speed processing and data security; Support external device expansion such as Bluetooth keyboard and wireless LAN to enhance operational flexibility.

Display screen and operation: Equipped with a 10.1-inch color WSVGA tiltable touch screen, built-in embedded web browser, operation logic similar to a tablet, supports custom homepage taskbar, only displays high-frequency usage functions, reduces operation clutter; Simultaneously supporting accessible designs such as tilted panels and universal paper tray handles.

Paper processing capability

Capacity configuration: The standard 4-drawer design can accommodate 2280 sheets of paper, while the serial drawer version has a standard capacity of 3520 sheets; The maximum capacity can be expanded to 4780 sheets (4 drawers) or 6020 sheets (series drawers), and the MP2502B 2500 large capacity feeder can be optionally selected to further enhance paper storage.

Supports sizes and types: can handle regular paper from 3.9 “× 5.8” to 13 “× 19”, banners from 12 “× 47”, and envelopes; The paper weight range is 16 pounds Bond to 140 pounds Index (standard drawer), 16 pounds Bond to 110 pounds Cover (bypass feed), suitable for various document printing needs.

Featured features and connectivity

Workflow optimization function

Elevate function: It can customize automated workflows based on enterprise business processes, simplify multi-step operations into “one click execution”, reduce manual operations and paper consumption, lower costs, and improve efficiency.

Print Around: When a printing task is stalled due to paper size, type, or toner issues, allow other tasks to print first to avoid clogging the print queue.

Scan and fax enhancement: Supports scan preview (viewing, rotating, adjusting scanned documents on the touch screen), fax preview (viewing received faxes before deciding whether to print, saving consumables), and scans can be directly saved in Office formats such as DOCX, XLSX (with embedded OCR enabler).

Connection and compatibility

Mobile and wireless connectivity: Supports AirPrint ® (Apple devices) Mopria ® (Android devices) Wi-Fi Direct, Paired with the e-BRIDGE Print&Capture application, it enables direct printing and scanning of documents from mobile phones/tablets to be sent back to mobile devices.

Cloud service integration: Through the e-BRIDGE Plus series of applications, it supports OneDrive access ®  for Business、SharePoint ®  Online、Exchange Online、Google Drive ™、 DropBox ®  Wait for cloud storage to print documents, or scan documents and upload them directly to the cloud platform.

System and protocol compatibility: compatible with Windows ® (8.1/10/Server 2012 and above) Macintosh ® (macOS X 10.7.4 and above) Unix ®、 Linux ®  System; Support printing protocols such as SMB, LPR/LPD, IPP, Port 9100, etc., to meet different office network environments.

Safety and Environmental Protection Standards

Security protection system

Data Security: 320GB SED supports automatic data invalidation (ADI) and data overwrite to prevent hard disk data leakage; Optional FIPS 140-2 certified SED, compliant with government level security requirements; Support IPsec encryption to ensure secure data transmission between devices and networks.

Access control: supports user authentication (device side/Windows domain/LDAP server), MAC/IP address filtering (10 groups each), role-based access control (RBAC), secure PDF, firmware digital signature, to prevent unauthorized operations and malicious attacks.

Compliance certification: Through HCD-PP certification and CC certification (ISO/IEC15408), it meets strict security compliance requirements and is suitable for industries sensitive to data security, such as finance and government.

environmental performance

Certification standard: Compliant with ENERGY STAR ®  V3.0 certification, EPEAT Gold registration, use RoHS compliant materials, use recycled plastics to reduce environmental impact.

Energy saving design: Supports super sleep mode (with a power consumption of only 0.6W), low monthly average energy consumption (TEC value), and reduces operating costs; The green information function of e-BRIDGE Plus can display environmental contribution data on the touch screen, guiding efficient use.

Optional accessories (table display)

Accessory category, model, and function

Auxiliary operation accessories GR1330 (accessory tray), GR9000 (Bluetooth keyboard), GR1340 (10 key numeric keypad)

Binding and output accessories MJ1111B (50 page console stapler), MJ1112B (50 page saddle stitch stapler), MJ6106N (punching unit), KA6551 (side paper tray)

Connection and security accessories GD1370N (fax unit/second fax line), GN4020 (wireless LAN/Bluetooth module), GE1230 (FIPS 140-2 SED), GP1080 (IPsec enabler)

Function extension accessories GS1080NODE (embedded OCR enabler, authorized by seat), GS1090NODE (multi workstation printing enabler, authorized by seat) GB2300NODE(e-BRIDGE Plus for Business V3.0)

Paper expansion accessory MP2502B (2500 large capacity feeder, only supports LT size)

Key issues

Question 1: What are the core advantages of Toshiba e-STUDIO 7516AC series in high load office scenarios? What are the corresponding key parameter supports?

Answer: The core advantages are high speed, high capacity, and high stability, which can meet the high-frequency and large-scale document processing needs of large workgroups. The specific parameter support is as follows:

Speed support: Color printing/copying speed up to 75 PPM, black and white up to 85 PPM, first print output time as short as 4.1 seconds (black and white) and 5.4 seconds (color), preheating time of about 20 seconds, reducing waiting time;

Capacity support: The maximum monthly copying capacity is up to 600K pages, with a standard paper capacity of up to 3520 sheets (series drawer), and can be expanded to 6020 sheets+2500 sheets (optional feeder), reducing frequent paper additions;

Stability support: Equipped with Intel Atom dual core processor, 4GB memory, and 320GB self encrypting hard drive, the hardware configuration is strong, and it also supports Print Around function to avoid printing queue congestion and ensure smooth operation under high loads.

Question 2: How does this series of printers ensure the security of sensitive documents for enterprises? What levels of security measures are covered?

Answer: To ensure the security of sensitive documents through four levels of data storage security, transmission security, access control, and compliance authentication, specific measures are as follows:

Data storage security: Equipped with a 320GB self encrypting hard drive (SED), supporting automatic data invalidation (ADI) and data overwrite functions to prevent data leakage after the hard drive is stolen or the device is scrapped; Optional FIPS 140-2 certified SED, meeting government level encryption standards;

Data transmission security: Supports IPsec encryption protocols (IKEv1/IKEv2) to ensure the security of data transmission between devices and networks, avoiding interception or tampering during the transmission process;

Access control security: supports multi-dimensional authentication (device authentication, Windows domain authentication, LDAP server authentication), MAC/IP address filtering (10 groups each), role-based access control (RBAC), only authorized users can operate copy/print/scan/fax functions; Simultaneously supporting secure PDF and firmware digital signatures to prevent malicious software attacks;

Compliance certification and security: Through HCD-PP certification and CC certification (ISO/IEC15408), it complies with internationally recognized information security assessment standards to ensure the compliance and reliability of security measures.

Question 3: From the perspective of environmental protection and cost control, what are the design highlights of this series of printers? What practical benefits can it bring to the enterprise?

Answer: The highlights of environmental protection and cost control design are concentrated in three aspects: energy conservation and consumption reduction, consumables optimization, and process paper reduction. The actual benefits are as follows:

Energy saving and consumption reducing highlights: compliant with ENERGY STAR standards ®  V3.0 certification and EPEAT Gold registration, supporting super sleep mode (power consumption of only 0.6W), with low monthly average energy consumption (TEC value); Actual benefits: Reduce electricity expenses while lowering the company’s carbon footprint, in line with green office policies;

Highlights of consumables optimization: Large toner capacity (color 39200 pages/black 106600 pages, 5% coverage), reducing toner replacement frequency; Support fax preview (view before printing), scanning and electronicization (save directly to Office format); Actual benefits: Reduce the procurement cost of consumables such as carbon powder and paper, and decrease the labor cost of replacing consumables;

Highlights of process paper reduction: Elevate function simplifies multi-step processes into one click automated operations, reducing manual paper processes; Support cloud scanning/printing to reduce the circulation of paper documents; Actual benefits: Reduce paper consumption while improving work efficiency, indirectly reducing the time and storage costs associated with managing paper documents.

TOSHIBA CANVIO BASICS portable hard drive

Product Overview

1.1 Basic Information

Product Name: TOSHIBA CANVIO BASICS Mobile Hard Drive

Packaging components: Consists of three types of fixed items, as shown in the table below:

Component name, quantity, and purpose

CANVIO BASICS hard disk body 1 core storage carrier

One USB 3.0 Micro-B cable connects the hard drive to the computer, transferring data and providing power

1 set of supporting documents (including security guidelines) including multilingual operation instructions, security specifications, and compliance statements

Language version: covering more than 20 languages, including English (EN), German (DE), French (FR), Italian (IT), Spanish (ES), Turkish (TR), Russian (RU), Ukrainian (UK), etc., to meet the needs of users in different regions.

Interface specifications: Adopting USB 3.2 Gen 1 interface (compatible with USB 3.0/2.0), with Micro-B connector on the hard drive end and Type-A connector on the computer end.

System requirements

2.1 Operating System Adaptation

Windows system:

Supported versions: Windows 10, Windows 8.1;

Format requirement: Pre installed with NTFS file system, can be used directly without additional formatting.

MacOS system:

Supported versions: macOS v10.15 (Catalina), v10.14 (Mojave), v10.13 (High Sierra);

Format requirement: Must be reformatted (default format incompatible), it is recommended to format to APFS or Mac OS Extended format supported by macOS.

2.2 Hardware and Power Requirements

Port requirements: The computer requires one free USB 3.0 or USB 2.0 port (USB 3.0 is backward compatible with USB 2.0, and if a USB 2.0 port is used, the transfer speed will be reduced to USB 2.0 level);

Power supply method: Bus powered, no external power supply required, all current is provided through USB port;

Disabled devices: Cannot connect passive USB hubs (without independent power supply), keyboard/mouse and other USB device expansion interfaces, which may result in insufficient power supply or data transmission errors.

Operation process

3.1 Connection steps

Hard drive connection: Insert the USB 3.2 Gen 1 Micro-B connector into the corresponding port of the hard drive (note polarity, do not forcefully plug or unplug);

Computer connection: After the computer is fully powered on and the operating system is loaded, insert the USB Type-A connector into the USB Type-A port of the computer;

Status confirmation:

Windows: The Power/Data indicator light is on, the hard drive is automatically mounted, and a new hard drive icon is displayed in “My Computer”;

Mac: The Power/Data indicator light is on, the hard drive is ready directly, and the desktop displays the hard drive icon.

3.2 Secure uninstallation

It is strictly prohibited to directly unplug the cable (which may cause data loss or physical damage to the hard drive), and it should be operated according to the system type:

System type uninstallation steps

Windows 1. Click on the “Hardware and Pop Up Media” icon on the taskbar;

2. Select TOSHIBA hard drive from the pop-up list;

3. After receiving the “Safely Removable” notification, click “OK” and unplug the cable

Mac 1. Ctrl click on the desktop hard drive icon and select “Eject”;

2. Alternatively, simply drag the hard drive icon to the trash can;

3. After the icon disappears, unplug the cable

3.3 Cleaning and Maintenance

Cleaning prerequisite: The hard drive must be physically disconnected from the computer first (unplug the USB cable);

Cleaning supplies: Use standard cleaning agents (such as neutral cleaning agents), and prohibit the use of corrosive liquids (such as phenol, gasoline, diluents, etc.);

Operation requirements: After cleaning, wipe off any residual liquid on the surface to prevent liquid from seeping into the interior of the hard drive and causing a short circuit.

Frequently Asked Questions (FAQ) and Troubleshooting

4.1 Frequently Asked Questions and Answers

Problem Description Answer

Does Windows require an additional USB driver? No need, the driver is integrated into the Windows system and plug and play

2. Can the computer system be started from this hard drive? No, Windows does not support booting the system from an external hard drive

Why does a hard drive not require a fan? Adopting optimized heat dissipation structure, it can naturally dissipate heat and achieve near silent operation (without fan noise)

Why does Windows display a smaller capacity than indicated? Differences in calculation methods: Manufacturers use decimal (1TB=1000GB), systems use binary (1GB=1024MB), and 1TB hard drives display approximately 931GB

Can I copy the operating system to another computer? No, you need to reinstall according to the installation guide provided by the operating system manufacturer. Simple copying cannot achieve system operation

4.2 Fault Handling Plan

Fault 1: The computer does not recognize the hard drive at all

Troubleshooting steps: ① Check if the USB cable connection is secure; ② If using a USB hub, confirm that the hub has independent power supply; ③ If using an expansion card, check if the expansion card is working properly and update the firmware.

Fault 2: The hard drive displays’ unable to start device ‘

Possible reasons: ① Insufficient power supply (check if the USB port is in good contact); ② Hard disk hardware malfunction (requires contact with after-sales maintenance).

Fault 3: The hard drive is not displayed in “My Computer”, but it exists in the Device Manager

Solution steps:

Right click on “My Computer” and select “Manage”;

Enter ‘Disk Management’ and confirm that the hard drive is in the list;

Right click on the hard disk partition and select “Delete Partition” (note: data may be lost);

Right click on unallocated space and select ‘New Primary Partition’, then follow the wizard to complete the setup;

Confirm formatting (recommended NTFS format), and once completed, it can be displayed.

Fault 4: When formatting, it prompts’ unable to complete formatting ‘

Reason: Mostly caused by the use of FAT file system (insufficient compatibility);

Solution: Replace with NTFS file system and reformat.

Compliance and environmental requirements

5.1 Certification Compliance

CE certification: The product complies with relevant EU directives (such as the EMC electromagnetic compatibility directive), and the responsible party is Toshiba Electronics Europe GmbH (Dusseldorf, Germany);

UKCA certification: compliant with British standards, responsible by Toshiba Electronics Europe GmbH UK branch (Surrey, UK);

REACH compliance: Toshiba will provide users with relevant information on chemical substances in its products to comply with the EU’s Chemical Registration, Evaluation, Authorization and Restriction Regulations.

5.2 Environmental Protection Disposal

Disposal requirements: The product must bear the label “Prohibited from being disposed of as household waste” and must be handled by a professional industrial waste organization (such as a qualified recycler);

Special regional requirements: Türkiye market shall comply with AEEE regulations (electronic waste recycling regulations);

Risk Warning: Self disassembly may cause capacitor explosion or release of toxic gases, violating the Waste Disposal and Cleaning Law.

TOSHIBA TOSBERT TM VF-nC1 Industrial Inverter

Product Overview

1.1 Basic Information

Model: TOSBERT TM VF-nC1 Industrial Inverter

Applicable motor: only for three-phase induction motors, cannot drive single-phase motors

Power and voltage specifications: covering three voltage levels, with specific parameters as shown in the table below:

Voltage level, power range (kW), model example, output current (A), suitable motor capacity (kW)

Single phase 100V level 0.1-0.75 VFNC1S-1001P 0.7-4.0 0.1-0.75

Single phase 200V level 0.2-2.2 VFNC1S-2002P 1.4-10.0 0.2-2.2

Three phase 200V level 0.1-2.2 VFNC1-2001P 0.7-10.0 0.1-2.2

Single phase 200V level (with filter) 0.2-2.2 VFNC1S-2002PL 1.2-10.7 0.2-2.2

Core control method: Adopting sine wave PWM control, the output frequency range is 0.5-200Hz (default 0.5-80Hz), and the voltage/frequency characteristics can be adjusted through parameters (V/f constant, sensorless vector control).

Safety regulations

2.1 Warning System

The manual divides safety warnings into two levels, clarifying the consequences of risks and operational requirements:

Typical scenario examples of warning type meanings

Warning: Incorrect operation may result in death or serious injury. Disassembling the front cover while live, connecting input power to output terminals, and operating without grounding

Incorrect handling of the solution may result in minor injuries or property damage. Touching the heat sink, using incompatible chemicals, and installing in a vibrating environment

2.2 Mandatory Safety Requirements

Grounding: D-type grounding (formerly Class 3 grounding) must be used, and the grounding wire diameter should be ≥ 3.5mm ² (refer to the terminal specification table for details) to ensure safe conduction of leakage current in case of fault.

Power off waiting: After disconnecting the input power, wait for at least 15 minutes to confirm that the charge light is off and the DC main circuit voltage is ≤ 45V before touching the terminal.

Installation base: It needs to be fixed on a metal base that can withstand the weight of the equipment to prevent it from falling; Choose NEMA 3R protection model (such as 5000 series) for outdoor/harsh environments.

Emergency stop: It must be equipped with an emergency stop device independent of the frequency converter (such as mechanical braking), and the frequency converter alone cannot achieve immediate shutdown.

Parameter settings

3.1 Parameter Classification and Core Parameters

Parameters are divided into three categories: basic parameters, extended parameters, and special parameters. The core parameters and functions are as follows:

Parameter Category Parameter Code Function Description Adjustment Range Default Values Key Role

Basic parameter CMod instruction mode selection (source of run/stop instructions) 0- Terminal board/1- Panel 1 Determine control mode

FMod frequency setting mode selection: 0- Terminal board/1- Panel, etc. 2. Determine the frequency adjustment method

ACC/DEC acceleration time 1/deceleration time 1 0.1-3000 seconds 10.0s to prevent current overload during startup/shutdown

FH/UL maximum frequency/upper limit frequency 30-200Hz/0.5-FH 80Hz/80Hz limits the maximum operating frequency of the motor

Extended parameter F300 PWM carrier frequency 2/4/8/12/16kHz 12kHz balanced motor noise and inverter losses

F250-252 DC braking parameters (starting frequency/current/time) 0.0-FHHz/0-100/0-20s 0.0Hz/50%/1.0s to achieve rapid shutdown

OLn electronic thermal protection characteristics 0-7 (corresponding to different protections) 0 adaptation standard motor/VF motor protection

Special parameter RUL wizard function (quick setting) 0-5 (5-class wizard) 0 Simplified parameter configuration (such as basic settings)

RUH History Record Function – Display the Last 5 Modified Parameters

3.2 Parameter Setting Process

Enter setting mode: Press the MON key to switch to “parameter setting mode” (display “RUH”);

Parameter selection: Use the △/▽ keys to select the target parameter (such as CMod);

Modify parameters: Press the ENT key to enter editing, and then use the △/▽ keys to adjust the values;

Save parameters: Press the ENT key again, and the parameters and values will alternate to indicate successful saving;

Reset default: Set the basic parameter “Eyp” to 3 to restore all parameters to their factory default values (with the need to shut down first).

Installation and wiring

4.1 Installation environment requirements

Temperature: Operating environment temperature * * -10 ℃ -50 ℃ * *. When the ambient temperature is greater than 40 ℃, the warning label on the top of the equipment should be removed and the rated output current should be reduced (such as the current of the 2007P model dropping from 4A to 3.6A at 40-50 ℃);

Humidity: Relative humidity of 20% -93%, no condensation;

Vibration: Vibration acceleration<5.9m/s ² (10-55Hz), avoid installing near strong vibration equipment such as machine tools;

Other: No dust, corrosive gases, oil mist, keep away from heat sources (such as transformers, heaters).

4.2 Terminal Wiring Specification

Main circuit terminals:

Screw specifications: M3 (low power)/M3.5 (high power), tightening torque of 0.8N · m/1.0N · m respectively;

Wiring requirements: Connect the input (R/L1, S/L2, T/L3) to the power supply, and the output (U/T1, V/T2, W/T3) to the motor. Reverse connection is prohibited as it may damage the inverter;

Grounding terminal: It needs to be independently grounded with a wire diameter of ≥ 3.5mm ² (refer to section 10.1 wiring table).

Control circuit terminals:

Screw specifications: M2/M3, wire diameter 0.3-1.5mm ², sheath stripping length 5-6mm;

Wiring taboos: Control circuit and main circuit wiring should be separated (not parallel, not bundled, different conduit) to avoid interference.

4.3 Wiring precautions

It is prohibited to connect capacitive devices (such as noise filters and surge absorbers) on the output side, as this may cause a fire;

The length of the main circuit line is ≤ 30m, and if it exceeds this limit, the wire diameter needs to be increased (for example, for a 200V level 0.75kW motor, a wire length>30m requires a wire of ≥ 2.5mm ²);

When multiple inverters share a power supply, each one needs to be equipped with an independent MCCB (circuit breaker) to avoid the spread of faults.

Operation and monitoring

5.1 Operating Mode

Panel control: Set CMod=1, start with RUN key, stop with STOP key, adjust frequency with △/▽ key;

Terminal control: Set CMod to 0 and control operation by short circuiting the F-CC (forward rotation) and R-CC (reverse rotation) terminals;

Jog operation (JOG): Set the input terminal function to “JOG”, the motor runs at a fixed frequency of 5Hz when short circuited, and stops freely after disconnection;

Preset speed operation: By allocating SS1-SS4 terminals (a total of 4 terminals), 15 levels of preset speed can be achieved (F287-F294 parameters need to be set).

5.2 Status Monitoring

Monitoring content: The output frequency, load current (%/A), input voltage (DC), output voltage (%/V), cumulative running time (0.01=1 hour), etc. can be viewed through the “status monitoring mode” (press MON button twice);

Fault display: When tripped, the LED displays a fault code (such as “OC1” indicating acceleration overcurrent), and the FL relay operates (fault output);

Alarm message: Non trip warning (such as “rEr” indicating retry), only prompts not to stop the machine, and attention should be paid to the equipment status.

Fault handling

6.1 Common tripping faults and remedies

Fault code, fault type, possible cause, remedial measures

OC1 acceleration overcurrent acceleration time is too short, motor impedance is too small, extending ACC time (such as changing from 10s to 20s), checking motor insulation

OP2 deceleration overvoltage deceleration time too short, excessive regenerative energy prolongs dEC time, F305 is enabled (overvoltage limited operation)

OH inverter overheating fan fault, poor ventilation, environment overheating. Replace the fan, clean the ventilation opening, and improve environmental heat dissipation

OL2 motor overload, excessive load, long low-speed operation time to reduce load, adjust electronic thermal protection level (OLn=4 compatible with VF motor)

6.2 Fault reset method

Panel reset: In the shutdown state, press the STOP button to display “LLr”, then press the STOP button to reset (the fault needs to be eliminated first);

External reset: Short circuit the control terminal RST to CC and disconnect it (RST function needs to be assigned first);

Power off reset: Disconnect the input power supply, wait for 15 minutes, and then power it back on (used in emergency situations, not recommended for frequent operation).

Maintenance and Quality Assurance

7.1 Regular Maintenance Plan

Maintenance Type Cycle Maintenance Content Precautions

Daily inspection of environmental temperature, vibration and noise, load current, and alarm light status without stopping the machine. Visual and instrument checks are required

During the 3-6 month maintenance cycle, terminal tightening, dust removal (ventilation/circuit board), and capacitor inspection must be carried out by cutting off the power for 15 minutes and confirming that the voltage is ≤ 45V before operation

Long term storage: Power on for more than 5 hours every 2 years (motor disconnected), gradually increase the voltage with a transformer to restore capacitor performance, and avoid direct commercial power supply

7.2 Service life and replacement of vulnerable parts

Cooling fan: With a lifespan of approximately 30000 hours (2-3 years of continuous operation), it should be replaced in case of abnormal noise or stoppage;

Electrolytic capacitor: The lifespan of the smoothing capacitor in the main circuit is about 5 years (normal environment). Check for no leakage and ensure that the safety valve is not protruding. Otherwise, replace it;

Fuse: with a lifespan of about 10 years, regularly inspect the appearance, and replace it with the same specification (such as CC/J grade 8A) after melting.

7.3 Warranty Scope

Warranty period: 12 months from the delivery date, only covering the frequency converter host;

Free repair: Parts malfunctions that occur under normal use (such as fans and capacitors);

Disclaimer:

Improper use (such as overload, misconnected power supply);

Self modification/repair;

Natural disasters (fire, earthquake) or abnormal voltage;

Out of range applications (such as driving single-phase motors).

Compliance and Disposal

8.1 Certification Compliance Requirements

CE certification:

EMI filters need to be installed on the input side (such as EMFA2006Z suitable for 200V low power);

Shielded wires are used for the main circuit/control circuit, and the shielding layer is grounded (with a distance of less than 10cm from the inverter);

UL/CSA certification:

Use copper wires above 75 ℃, equipped with CC/J level fuses (such as 4A fuses for the 2002P model);

Branch circuit protection must comply with local electrical regulations (such as NEC in the United States and CEC in Canada).

8.2 Equipment disposal

Mandatory requirement: Waste frequency converters must be disposed of by professional industrial waste disposal institutions (self disassembly is prohibited);

Risk Warning: Self disposal may lead to capacitor explosion and release of toxic gases, violating the Waste Disposal and Cleaning Law;

Contact organization: You can contact Toshiba’s regional branches at the end of the manual to obtain compliance disposal channels.

TOSHIBA TE2 series low-voltage digital solid-state soft starter

Equipment specifications and core functions

1. Basic electrical specifications

Input voltage 208-600VAC (± 10%), 50/60Hz three-phase AC (18-48A model optional single-phase)

Output current of 18-1250A (continuous rated) is distinguished by model, for example, TE2-18-BP is 9-18A, TE2-1250-BP is 625-1250A

Starting capacity 500% rated current, 20 seconds (standard duty); 60 second (heavy duty) SCR endurance capability

Control power supply 120VAC (standard), 240VAC (optional) to be provided by the customer, VA requirements according to model: 100VA for 18-48A, 1000VA for 1250A

Protection level: Open type (to be installed inside NEMA 1/12 enclosure), anti dust/splash requires additional enclosure

Communication interface RS485 Modbus RTU baud rate 9600/19200/38400bps, address 1-247

2. Core functions and protective features

Start mode voltage ramp (VR) F010=1/3, initial voltage 0-100% (F011/F015), ramp time 1-120 seconds (F013/F017)

Current ramp (CR) F010=2/4, initial current 0-600% FLA (F012/F016), current limit 200-600% FLA (F014/F018)

Dual slope switching external contact point control (TB1-6/7), supporting VR+VR, CR+CR, VR+CR, CR+VR combination

Jog voltage 5-100% (F019), time 1-20 seconds (F020), or current 100-500% FLA (F021)

Kick Start voltage 10-100% (F022), time 0.1-2 seconds (F023), used to break through high static friction loads

Protection function: Thermal overload protection NEMA Class 5-30 (when F003 is started and F004 is running), supports manual/automatic reset (F005)

Phase protection phase loss (current<12% CT value), phase imbalance (5-30%, F040), phase rotation (ABC/ACB, F098)

Voltage protection overvoltage 1-10% (F032), undervoltage 1-20% (F034 startup/F036 operation), voltage imbalance 1-30% (F030)

Current protection overcurrent 100-300% FLA (F042), undercurrent 10-90% FLA (F044, load loss detection), grounding fault 5-90% CT value (F046)

Mechanical protection start interval lock (1-60 minutes, F050), hourly start limit (1-10 times, F049), reverse lock (1-60 minutes, F048)

Installation and wiring

1. Installation requirements

Environmental temperature conditions: 0-40 ° C (working), -5-40 ° C (storage); Humidity: 5-95% RH (no condensation) Avoid dust, corrosive gases, and vibration (<0.5G)

The installation spacing should be ≥ 25mm (1 inch) on both sides and ≥ 100mm (4 inches) on both sides to ensure heat dissipation. Multiple units should be placed side by side with gaps left

Cooling direction: The ribs of the cooling fins are vertically installed to assist with fan cooling, ensuring smooth airflow

The shell requirement is that open models should be installed in NEMA 1 (indoor) or NEMA 12 (dustproof and splash proof). The size of the inner and outer shells of the shell should meet the requirements of heat dissipation: for example, the shell volume of 18-481 should be ≥ 0.05m ³

2. Wiring configuration (key terminals)

(1) Power wiring (main circuit)

L1/L2/L3 (R/S/T) main power input three-phase 208-600VAC, requires circuit breaker/isolation switch TE2-18-BP: 10AWG, torque 35in lbs (M5 bolt)

T1/T2/T3 (U/V/W) motor output is connected to a three-phase motor, and reverse input/output TE2-1250-BP: 4 × 500kCMIL, torque TBD is strictly prohibited

The grounding terminal equipment shall be grounded according to NEC specifications, with a wire diameter not less than 1/2 of the phase wire. For example, a 10AWG phase wire shall be paired with an 8AWG grounding wire

(2) Control wiring (TB1 DC 24V, TB2 AC 120/240V)

TB1 (DC 24V) 1-3 3-wire control (Start/Stop) 1 connected to Start (NO), 2 connected to the common terminal, 3 connected to Stop (NC)

External interlock (NC) 4-5 connected to low oil level/high temperature switch, factory jumper needs to be removed

6-7 dual slope switch to external contacts, close and activate slope 2

7-8 Jog: Connect to external contacts, close to activate Jog (requires Start command)

9-10 analog output (4-20mA) connected to PLC/instrument, monitoring current/voltage/thermal capacity (F108 setting)

11-12 fault output (optocoupler Triac) connected to PLC, conducting in case of fault (240VAC/50mA max)

TB2 (AC control power supply) 21-22 (A1-A2) control power supply input 120VAC (standard), requires 1A fuse connection

13-20 auxiliary relay outputs 3 relays: 2 SPDT (13-18), 1 SPST (19-20), 240VAC/5A

Parameter programming

1. Core mandatory parameters

The rated current (FLA) of F001 motor must be set to the FLA on the motor nameplate, otherwise the soft starter will not operate. Range: 50-100%. The maximum current of the soft starter is 9-18A, such as TE2-18-BP

The service factor (SF) of F002 motor is set according to the motor nameplate, affecting the FLA upper limit 1.0 range of 1.00-1.30. If SF ↑, F001 can be set within the range ↓

F003/F004 Start/Run Overload Level NEMA Class 5-30, Match Motor Overload Capacity 10 (Class 10) Set High Level (e.g. Class 20) during Start to Avoid False Alarm

F010 Slope Type Selection: Choose Voltage/Current Slope and Double Slope Combination 1 (VR1+VR2). For heavy loads, choose CR, and for light loads, choose VR

F014/F018 maximum current limit limits the starting current and protects the power grid and motor by 350%. When the FLA power grid capacity is small, set it low (such as 250%), and when overloaded, set it high (such as 500%)

2. Programming operation process

Enter programming mode: In the status display mode (default display of A-phase current), press the 【 Fn 】 key to enter the F001 parameter interface.

Adjust parameters:

Press the ←/→ key to select the digit to be modified (flashing);

Press the 【 ↑/↓ 】 keys to adjust the value (long press for 2 seconds to start automatic stepping);

Press the 【 ENT 】 key to save and display ‘End’ for confirmation.

Password protection:

Set F070 to a non-zero value (1-999) to enable the password, and enter the password for the next modification;

If you forget your password, please contact Toshiba customer service to restore the factory settings (F071=2) without clearing the password.

Communication programming: Connect PLC/upper computer through RS485 Modbus and modify parameter registers (such as register address 0x0001 corresponding to F001).

Startup and troubleshooting

1. Initiation process and inspection

Step operation content Key checkpoints

1. Confirm that the wiring of the main power supply, motor, and control power supply is correct, the grounding is reliable, and there is no looseness

The required parameters F001 (FLA), F002 (SF), and F010 (slope type) for parameter settings have been correctly configured

3. Power on test: Connect the control power supply, the “Power On” LED lights up and displays 【 0000. 】 (phase A has no current)

Press the Start button to start the test, the motor accelerates according to the set slope, the “At Speed” LED lights up (the motor reaches full speed), and the bypass contactor is closed

5. If the machine stops during startup, check the fault code (such as “oLA”=overload, increase F003)

2. Common faults and troubleshooting

Troubleshooting steps for fault codes and causes

NFLA motor FLA not set (F001=0) 1. Enter programming mode; 2. Let F001 be the motor nameplate FLA; 3. Restart after saving

1. Check if the main power supply L1/L2/L3 is out of phase during PLc operation; 2. Check if the motor wiring T1/T2/T3 is loose; 3. Confirm that the phase loss protection (F101) has not been mistakenly enabled

Overload during oLA startup: 1. Check if F003 (startup overload level) is too small (if set to Class 5), it can be increased to Class 15; 2. Check if the load is too heavy, reduce the starting load or increase the current limit (F014)

SSd SCR short circuit or no load 1. Disconnect the power supply and measure whether the SCR (L1-T1, L2-T2, L3-T3) is short circuited; 2. Confirm that the motor is connected (no load will report this fault)

Ground fault during GFc operation: 1. Check if the motor winding is grounded; 2. Check if the cable insulation is damaged; 3. Adjust the grounding fault threshold (F046) or delay (F047)

3. Fault recording and reset

Fault record: F085-F093 stores the last 3 faults, including fault codes (F085/F088/F091), timestamps (F086/F089/F092), and date stamps (F087/F090/F093).

Reset method:

Manual reset: After troubleshooting, press the [Reset] button. If there is an overload fault, wait for the motor to cool down (heat capacity H ≥ F059);

Automatic reset: F052 selects the fault type (such as 4=phase loss), F053 sets the reset frequency (1-10 times), 1 minute/time;

Remote reset: Disconnect the control power and reconnect it (applicable to scenarios without Reset button).

Maintenance and Appendix

1. Regular maintenance

Maintenance project cycle operation requirements

Clean the heat sink every 3 months (in dusty environments) and blow it with 80-100psi dry compressed air. Do not use chemicals/metal brushes

Check the power/control terminals for looseness every 6 months and tighten them again (according to torque requirements)

Fan inspection: Every year, listen to the running noise of the fan. If there is any abnormality, replace it (with a lifespan of 3 years/30000 hours)

Capacitor inspection: The main circuit capacitor has a lifespan of 10 years/73000h every 5 years. If it exceeds the lifespan, it is recommended to replace it

Backup parameters every year through BSD Configurator to avoid loss

2. Important Appendix Content

Appendix 1 (Slope Details): Detailed explanation of the differences in VR/CR slope curves. It is recommended to use VR for centrifugal pumps and CR for long conveyor belts.

Appendix 2 (Pump Flex Deceleration): Used for soft stop of pumps to avoid water hammer effect, it is necessary to set the starting deceleration voltage (F025), stopping voltage (F026), and deceleration time (F027).

Appendix 3 (Password Protection): The process for handling lost passwords requires contacting Toshiba customer service for unlocking methods.

Appendix 4 (External Overload): When multiple motors are controlled or started by bypass, an external overload relay (OLR) is required. The wiring example is shown in document APP4.2.

Appendix 5 (Parameter Record): A blank table is used to record the parameters modified by the user for easy maintenance and traceability.

ABB Sace BSD series brushless servo drive

Equipment Overview

1. Specification of servo amplifier

Model Applicable Motor Capacity Power Type Key Parameters

BSD0100 BSM0100 (100W) single-phase 200-230V carrier frequency 10kHz, overload capacity 300%/about 3 seconds

BSD0200 BSM0200 (200W) single-phase 200-230V-

BSD0400 BSM0400 (400W) single-phase 200-230V-

BSD0750 BSM0750 (750W) single-phase/three-phase 200-230V-

BSD1000 BSM1000 (1000W) three-phase 200-230V-

BSD1500 BSM1500 (1500W) three-phase 200-230V-

BSD2000 BSM2000 (2000W) three-phase 200-230V-

2. Specification of servo motor

Series model Capacity Rated speed Rated torque Encoder

Low inertia BSM0100 100W 3000r/min 0.318N · m 17 bit serial

Low inertia BSM0200 200W 3000r/min 0.637N · m 17 bit serial

Low inertia BSM0400 400W 3000r/min 1.27N · m 17 bit serial

Low inertia BSM0750 750W 3000r/min 2.39N · m 17 bit serial

Medium inertia BSM1000 1000W 2000r/min 4.77N · m 17 bit serial

Medium inertia BSM1500 1500W 2000r/min 7.16N · m 17 bit serial

Medium inertia BSM2000 2000W 2000r/min 9.55N · m 17 bit serial

3. Model coding rules

Servo amplifier: Only specify power, such as the power corresponding to “XXXX” in “BSDXXXX” (0100=100W).

Servo motor: format is “BSMXXXXXX”, where “XXXX”=power, “C”=shaft type (C=keyway, L=flat shaft), “N/B”=brake (N=none, B=present), “00/01″=option (00=none, 01=oil seal).

Installation requirements

1. Installation of servo motor

Project Requirements Remarks

Storage environment temperature -20 ° C~60 ° C, humidity 10% -90% RH (no condensation), the same requirement applies when equipped with gear heads

Working environment temperature -10 ° C~40 ° C, humidity 10% -90% RH (no condensation), temperature with gear head 0 ° C~40 ° C

The installation direction can be horizontal, downward, or upward (in accordance with IEC standards IMB5/L51, etc.), and the encoder end should not be subjected to force

Load limit radial load (127N-510N), axial load (19N-253N) refer to Table 2-5 in the document, such as BSM0100 radial 127N

Cable protection for mobile scenarios requires drag chains with a maximum bending radius to avoid oil/water immersion

2. Installation of servo amplifier

Project Requirements Remarks

Storage environment temperature -20 ° C~85 ° C, humidity 10% -90% RH (no condensation), altitude ≤ 1000m, no dust/corrosive gas

Working environment temperature -10 ° C~55 ° C, humidity 10% -90% RH (no condensation), non drip/dust-proof, multiple installations require spacing

Installation direction Upright direction (horizontal marked with “BSD”) Heat dissipation requirements

When the installation spacing is ≥ 50mm at the top and ≥ 40mm at the bottom, and the spacing between multiple parallel units is ≥ 5mm and < 5mm, the rating needs to be reduced to 80% ED

Leave ≥ 70mm (for easy operation) for wiring in the front space, with a depth of 165mm for 1.0kW and below, and 185mm for 1.5kW and above

Wiring specifications

1. Power wiring

Equipment power type, wiring terminal voltage range, frequency

Servo amplifier (0.4kW and below) single-phase L1, L2 200-230VAC (-10%~+10%) 50/60Hz

Servo amplifier (0.75kW) single-phase/three-phase L1, L2 (single-phase); L1, L2, L3 (three-phase) 200-230VAC (single-phase -10%~+10%, three-phase -15%~+10%) 50/60Hz

Servo amplifier (0.85kW and above) three-phase L1, L2, L3 200-230VAC (-15%~+10%) 50/60Hz

Control power supply (all models) single-phase sL1, sL2 200-230VAC (-10%~+10%) 50/60Hz

2. Key wiring taboos

Do not connect the commercial power supply (200V) to the U/V/W terminals of the servo motor (as it may burn the motor).

Do not connect the grounding wire (E) to the U/V/W terminal, and do not connect the U/V/W terminal in reverse (which may cause fire/malfunction).

It is prohibited to conduct voltage withstand, megaohm, and buzzing tests on the encoder terminal (CN2) as it may damage the encoder.

The distance between the serial I/O (CN1) and the motor power cable should be ≥ 10cm (to avoid interference).

Test Run

1. Three stage testing process

Key inspection items for stage testing content

The first stage servo amplifier and motor are tested separately (not connected to the machine). 1. Power wiring (L1/L2/L3); 2. Motor power supply (U/V/W) and encoder wiring; 3. Motor rotation direction (parameter # 04); 4. No alarm

In the second stage, connect to the upper control system (not connected to the machine). 1. Connect the signal lines of the upper system; 2. I/O signals (such as emergency stop EMG, overtravel ± OT); 3. Motor speed/torque (in accordance with instructions)

The third stage of testing after installing the machine (final state): 1. The firmness of the motor installation; 2. Machine travel; 3. Servo parameter adjustment (refer to Chapter 6); 4. Positioning accuracy

2. Origin regression requirements

After power failure and restart, the motor needs to be rotated at a speed of ≤ 100r/min for 372 ° or more (approximately 1.04 rpm) in order to correctly detect the Z-phase.

Parameter settings

1. Parameter configuration method

Keyboard operation: Switch to “Parameter Editing Mode” (PnO) for settings through a 4-digit 7-segment LED display and 4 buttons (MODE/ESC, SHIFT, ENT, ∧/∨).

BSD Configurator: Connected to CN3 via LAN cable (CAT. 5 direct connection), supports parameter read/write, batch transfer, and monitoring.

2. Core parameter table

Parameter number, parameter name, control mode, setting range, initial value, key role

#01 Command pulse compensation alpha position 1-32767 16 electronic gear ratio molecule, converting command pulse to mechanical stroke

#02 instruction pulse compensation β position 1-32767 1 electronic gear ratio denominator

#03 Pulse train input form: Position 0 (command pulse+symbol), 1 (forward/reverse pulse), 2 (two signals with a 90 ° phase difference), 1 matches the output type of the upper system pulse

#04 Rotation direction switching/output pulse phase all 0-30 set motor forward rotation direction (CCW/CW) and output pulse phase

#05 tuning mode position/speed 0 (automatic), 1 (semi-automatic), 2 (manual) 0 select servo gain tuning mode

#06 Load inertia ratio position/velocity GYS: 0.0-100.0; GYG: 0.0-30.0 5.0 (BSM low power), 1.0 (BSM high power) ratio of motor inertia to load inertia

#07 Automatic tuning gain position/speed 1-20 10 Adjust servo response speed (high value, fast response but prone to vibration)

#09 Control mode switch all 0 (position), 1 (speed), 2 (torque), 3 (position) ↔ 0 fixed or switchable control mode for speed)

3. Parameter Effectiveness Rules

The parameters marked as “Power” (such as # 03, # 04, # 09) need to be powered off and restarted to take effect; Other parameters (such as # 01, # 02, # 07) take effect in real-time.

Servo adjustment and special functions

1. Tuning method

Operation points for applicable scenarios of tuning types

Automatic tuning (# 05=0) Most conventional mechanical amplifiers automatically estimate the inertia ratio and set the optimal gain

Semi automatic tuning (# 05=1) inaccurate estimation of inertia ratio, manual setting of # 06 (load inertia ratio) in scenarios, amplifier automatically calculates gain

Manual tuning (# 05=2) Automatic/semi-automatic tuning failed. Manually set # 40 (position gain), # 41 (speed response), # 42 (speed integration time), etc

2. Special adjustment function

Vibration suppression control: By setting parameters # 60- # 63 (anti resonance frequency 0-3), mechanical vibrations (such as end effector vibrations of robotic arms) are suppressed within a frequency range of 5.0-200.0Hz.

Instruction Follow Control: Parameter # 55 is set (0=none, 1=follow, 2=follow+stop compensation) to achieve zero deviation following of pulse instructions, suitable for high rigidity machinery.

Inspection and maintenance

1. Regular inspection items

Equipment inspection content inspection frequency

Servo motor 1. Mechanical coupling deviation; 2. Smoothness of axis rotation; 3. Cable damage; 4. Loosening of screws regularly (e.g. monthly)

Servo amplifier 1. Dust accumulation; 2. Abnormal noise from the cooling fan; 3. Loose terminal screws; 4. No odor/signs of overheating regularly (e.g. monthly)

2. Service life and replacement of vulnerable parts

Component Standard Life Replacement Tips

Servo amplifier main circuit capacitor 73000h (10 years), lifespan shortened when ambient temperature exceeds 30 ° C

Replace the servo amplifier cooling fan when it makes abnormal noise or stops running after 30000 hours (3 years)

Replace servo motor bearings when vibration/abnormal noise occurs after 20000-30000 hours (3-5 years)

Replace the servo motor oil seal after 5000 hours of oil leakage

3. Common alarm handling

Alarm code, alarm reason, handling measures

OC1/OC2 overcurrent 1. Check the U/V/W wiring of the motor; 2. Check if the motor is short circuited/grounded; 3. Replace the amplifier

OL overload 1. Check motor load matching; 2. Extend the acceleration and deceleration time; 3. Reduce operating frequency

HV overvoltage 1. Check the power supply voltage; 2. Connect external regenerative resistors; 3. Extend deceleration time

LV undervoltage 1. Check the power supply voltage; 2. Confirm parameter # 26 (undervoltage detection) setting; 3. Improve the power environment

RS485 communication

1. Communication specifications

Project specifications

Signal level RS485

Communication method: 4-wire half duplex, asynchronous communication

Baud rate 9600/19200/38400bps (parameter # 83 setting)

Data format: 1 start bit, 8 data bits, 1 even check bit, 1 stop bit

Station number 1-31 (parameter # 2 setting)

Connect cable LAN line (CAT. 5 direct connection)

2. Core functions

Read: Multiple monitoring data (such as speed, torque), sequence mode, I/O signals, alarm history, system status.

Write: parameters, alarm reset, parameter initialization.

Search for products

Back to Top
Product has been added to your cart