Equipment Overview

Core function: AO801 is ABB Ability ™  System 800xA ®  The series of analog output modules has 8 unipolar analog output channels, which can perform self diagnosis periodically. When the internal power supply is too low, the module will enter the Initiat state (at this time, the module has no signal output).

Main features and advantages:

It has 8 output channels of 0… 20 mA and 4… 20 mA.

Equipped with OSP (Output Switching Protection) function, it can set the output to the preset state when an error is detected.

The analog output has short-circuit protection function and can be connected to ZP or+24 V.

Process and power connections are achieved through detachable connectors.

Basic information

Product Code: 3BSE020514R1

Type: Analog Output Module

Signal specifications: 0… 20 mA, 4… 20 mA

Number of channels: 8

Signal type: unipolar single ended

HART protocol support: not supported

SOE (Sequence of Events): Not supported

Redundant function: not supported

High integrity: not supported

Intrinsic safety: not supported

Mechanical specification: S800L

Technical Parameter

Resolution: 12 bits

Isolation method: Group level and ground isolation

Range of over/under range: ± 15%

Output load: Maximum 850 Ω

Error: 0.1%

Temperature drift: typical 30 ppm/° C, maximum 50 ppm/° C

Rise time: 10 µ s

Update cycle: 1 ms

Current limit: limited current output with short-circuit protection

Maximum on-site cable length: 600 meters (656 yards)

Rated insulation voltage: 50 V

Dielectric test voltage: 500 V AC

Power consumption: 3.8 W

+Bus current consumption of 5V module: 70 mA

+Bus current consumption of 24V module: none (-)

+24V external current consumption: 200 mA

Supported wire specifications: Solid wire: 0.05-2.5 mm ² (30-12 AWG); Stranded wire: 0.05-1.5 mm ² (30-12 AWG). Recommended torque: 0.5-0.6 Nm, wire stripping length: 6-7.5 mm (0.24-0.30 inches)

Diagnosis and indicator lights

Front panel indicator light: equipped with S (Status) indicator light, used to display operation or fault status, can indicate monitoring status, module errors, module warnings, channel errors and other information.

Environment and Certification

CE mark: Yes

Electrical safety standards: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201

Dangerous Place Certification: C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2

Classification Society Certification: ABS, BV, DNV, LR

Operating temperature: 0 to+55 ° C (+32 to+131 ° F), certified for+5 to+55 ° C

Storage temperature: -40 to+70 ° C (-40 to+158 ° F)

Pollution level: Level 2 (compliant with IEC 60664-1)

Corrosion protection: Complies with ISA-S71.04: G3 standard

Relative humidity: 5% to 95% (without condensation)

Protection level: IP20 in accordance with IEC 60529

Mechanical working conditions: comply with IEC/EN 61131-2

Electromagnetic compatibility: compliant with EN 61000-6-4 and EN 61000-6-2

Overvoltage category: Complies with IEC/EN 60664-1, EN 50178

Equipment category: Class I (grounding protection) in accordance with IEC 61140

RoHS compliance: Compliant with Directive 2011/65/EU (EN 50581:2012)

WEEE Compliance: Compliant with Directive/2012/19/EU

Size and weight

Width: 86.1 mm (3.4 inches)

Depth: 58.5 mm (2.3 inches)

Height: 110 mm (4.33 inches)

Weight: 0.24 kg (0.53 lbs.)