Product basic information
Product model: 6ES7231-0HC22-0XA0
Belonging to the Siemens SIMATIC S7-200 series, which is an analog input expansion module (EM 231)
Core positioning: A 4-channel analog input module designed specifically for S7-22X CPUs, supporting voltage and current inputs, using a 12 bit converter, suitable for analog signal acquisition in industrial automation scenarios. The document version date is March 22, 2017, and was last modified on March 16, 2017. The content may be subject to further adjustments.
Core electrical and input specifications
(1) Power supply and power consumption
Parameter category details
Input current load voltage L+(no load): maximum 60mA
-Backplane bus 5V DC: maximum 20mA
Typical power loss value of 2W
(2) Analog input characteristics
Specific specifications of input parameters
Number of channels: 4 differential analog input channels
Input type support – Supports: voltage input, current input
-Not supported: thermocouple, resistance thermometer, resistance input
Destruction limit – Voltage input: Maximum 30V
-Current input: maximum 32mA
Voltage input range (rated value) -0 to+5V (input resistance 10M Ω)
-0 to+10V (input resistance 10M Ω)
–2.5V to+2.5V (input resistance 10M Ω)
–5V to+5V (input resistance 10M Ω)
Current input range (rated value) 0 to 20mA (input resistance 10M Ω)
Cable length: Shielded cable up to 100m (up to sensor)
(3) Conversion and anti-interference performance
Performance parameter specifications
Maximum resolution of 12 bits (including symbol bit) when exceeding the range
Conversion time of 250 μ s per channel
Anti interference capability – interference voltage suppression for interference frequency f1 (50/60Hz): 40dB (DC to 60V)
-Suppression of interference voltage for frequency f=n × (f1 ± 1%) (f1 is the interference frequency): value not specified
-Common mode voltage: maximum 12V
Mechanical and Connection Specifications
(1) Size and weight
Dimensions: Width 71.2mm, Height 80mm, Depth 62mm
Weight: Approximately 183g
(2) Connection and isolation
Connection method: Plug in free I/O terminal (requires other wiring methods)
Potential isolation: There is no potential isolation between analog input channels
Functional characteristics
(1) Diagnosis and indication
Status indicator: Red external fault indicator light (EXTF), used to display the status of external faults
Diagnostic function: No explicit mention of complex diagnostic functions, only basic external faults are indicated through fault lights
Applicable restrictions
CPU compatibility: Only applicable to S7-22X series CPUs, not compatible with other series CPUs
Input type limitation: Temperature sensors such as thermocouples and resistance thermometers are not supported for input, only voltage and current signals can be collected

Leave a comment
Your email address will not be published. Required fields are marked *